7 Start-Up
System Manual Compact Systems
Page 68 of 110
HI 800 141 E Rev. 2.02
To clean up the resource configuration
1. Select a resource in the structure tree.
2. Click the
Online
button located on the Action Bar or select
Online
on the context menu.
3. In the
System Login
dialog box, enter a user group with administrator rights or write access.
The Control Panel appears in the workspace and displays the controller state.
4. In the
Online
menu, select
Maintenance/Service
->
Clean Up Configuration
.
5. The
Clean Up Configuration
dialog box appears. Click
OK
to confirm the action.
The configuration within the flash memory of the communication system has been cleaned up.
The clean-up function is not frequently needed.
A valid configuration is not affected by the clean-up process.
7.3.12
Setting the Date and the Time
To set the controller's time and date
1. Select a resource in the structure tree.
2. Click the
Online
button located on the Action Bar or select
Online
on the context menu.
3. In the
System Login
dialog box, enter a user group with administrator rights or write access.
The Control Panel appears in the workspace and displays the controller state.
4. In the
Online
menu, select
Start-Up
->
Set Date/Time
The
Set Date/Time
dialog box appears.
5. Select one of the following options:
-
Use the PADT date and time
- to transfer the time and date displayed for the PADT into
the controller.
-
User-defined
- to transfer the date and time from the two input boxes into the controller.
Make sure that the format used for date and time is correct!
6. Click
OK
to confirm the action.
The time and the date are set for the controller.
7.4
User Management in SILworX - CPU OS V7 and Higher
SILworX can set up and maintain an own user management scheme for each project and
controller.
7.4.1
User Management for SILworX Projects
A PADT user management scheme for administering the access to the project can be added to
every SILworX project.
If no PADT user management scheme exists, any user can open and modify the project. If a
user management scheme has been defined for a project, only authorized users can open the
project. Only users with the corresponding rights can modify the projects. The following
authorization types exist.
Type
Description
Security Administrator
(Sec Adm)
Security administrators can modify the user management scheme:
setting up, deleting, changing the PADT user management scheme,
and the user accounts and user groups, and setting up the default
user account.
Furthermore, they can perform all SILworX functions.
Read and Write (R/W)
All SILworX functions, except for the user management
Read only (RO)
Read-only access, i.e., the users may not change or archive the
projects.
Table 41: Authorization Types for the PADT User Management Scheme