System Manual Compact Systems
7 Start-Up
HI 800 141 E Rev. 2.02
Page 63 of 110
To get additional options for programming fault reactions in the user program, assign global
variable to
AO.Error Code
and
Module Error Code
. Refer to the manual of the compact system
or module for more details.
7.3.5
Configure Line Control
The pulse delay for line control is the time between setting the pulsed outputs to FALSE and the
latest possible reading of the signal on the corresponding input.
The default value is set to 400 μs. This value might need be increased if longer wires are used.
The maximum value is 2000 μs.
The minimum time for reading all inputs results in
pulse delay x number of pulses.
The pulsed outputs are usually set to TRUE and change to FALSE in succession for the
duration of the pulse delay once per cycle.
7.3.5.1
Required Variables
The following parameters must be created as global variables in the SILworX Global Variable
Editor:
Name
Type
Description
Initial
Value
Remark
Sum_Pulse
USINT
Number of pulsed
outputs
4
1...8, as required
Board_POS_P
ulse
UDINT
Module slot with pulsed
outputs
2
With compact devices, the
DOs are used in slot 1, 2 or
3, see Table 37.
With the F60, the slot (3...8)
is given.
Pulse_delay
UINT
Pulse delay
400
Value in µs
Maximum value: 2000 µs
F20: Pulse delay must
be ≥
500 µs.
Refer to the F20 manual.
T1
T2
...
T8
USINT
USINT
...
USINT
Pulse 1
Pulse 2
...
Pulse 8
1
2
...
8
Pulse 1...8, as required, must
match the number of pulsed
outputs.
Pulse_ON
BOOL
Initialization value for
pulsed outputs
TRUE
Activation of pulsed outputs
Table 35: Parameters for Line Control
The signal can be named freely; the names used in this manual are examples. All parameters
have the
Const
attribute.
The following table specifies the switch variables used in the example:
Name
Type
Description
Remark
S1_1_pulsed
S1_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 1
S2_1_pulsed
S2_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 2
FC_S1_1_pulsed
FC_S1_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 1
FC_S2_1_pulsed
FC_S2_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 2
Table 36: Switch Variables for Line Control