4 Start-Up
F3 DIO 16/8 01
Page 44 of 58
HI 800 177 E Rev. 1.01
System Signal
R/W
Description
0x0800
External supply L+ at DO+
DO.LSLB period [WORD]
W
Period [s] required for the line diagnosis
Range 1…100 s, 1 s steps
DO.LSLB monitoring time
[UINT]
W
Monitoring time for line diagnosis in [ms],
Range 1...50 ms, Default: 0 ms
Configuration for a two-pole channel
0
Channel used for a 1-pole
DO2[xx].Two-Pole [BOOL]
W
1
Channel used for a 2-pole
DO[xx].+Value [BOOL]
W
Output value for DO+ channels, one-pole (value: 0 or 1)
Output value for DO+ channels, two-pole, identical to DO- (Value
0 or 1)
DO[xx].-Value [BOOL]
W
Output value for DO- channels, one-pole (value: 0 or 1)
Output value for DO- channels, two-pole, identical to DO+
(Value: 0 or 1)
Configuration of line diagnosis
0 LSLB
1)
diagnosis is not performed
DO[xx].LSLB Monitoring
[BOOL]
W
1 LSLB
1)
diagnosis is performed
Line diagnosis with reduced voltage
0
Normal signal voltage level
1
Reduced signal voltage level
DO[xx].LS Monitoring with
reduced voltage [BOOL]
W
(Reduced signal voltage level only at DO[xx].LSLB
Monitoring = 1 effective!)
Common ground for each pair
(DO- outputs form the common ground)
0
No common ground for each pair
1
Common ground for each pair
DO[xx][xx].in pairs
[BOOL]
W
Default value: 0
Pair 1 = Channel 1 [01] and channel 2 [02]
Pair 2 = Channel 3 [03] and channel 4 [04]
Pair 3 = Channel 5 [05] and channel 6 [06]
Pair 4 = Channel 7 [07] and channel 8 [08]
1)
LS/LB
(short-circuit/open-circuits)
Table 28: ELOP II Factory - Digital Output System Signals