4 Start-Up
F3 DIO 16/8 01
Page 36 of 58
HI 800 177 E Rev. 1.01
4.3.3 Digital
Outputs
of F3 DIO 16/8 01
The following table presents the statuses and parameters for the output module (DO 8 03)
in the same order given in the SILworX Hardware Editor.
4.3.3.1
Module
Tab
The
Module
tab contains the following system parameters.
System Signal
Data
type
R/W Description
DO.Error Code
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
MOT test of safety shutdown returns a fault
0x0004
MOT test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
MOT test of output switch test pattern faulty
0x0020
MOT test of output switch test pattern
(shutdown test of the outputs) faulty
0x0040
MOT test active shutdown via WD faulty
0x0080
FTT test of monitoring time returns a fault
0x0100
FTT read back of monitoring time returns a
fault
0x0200
All outputs are switched off, total current
exceeded
0x0400
FTT test: 1st temperature threshold
exceeded
0x0800
FTT test: 2nd temperature threshold
exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
0x2000
FTT test: Monitoring of auxiliary voltage 2:
Low voltage
0x4000
Flipflop of the voltage monitoring (18V)
provides low voltage
0x8000
MOT test of monitoring time returns a fault
DO.Line
Monitoring Time
UINT
W
Monitoring time for line diagnosis in [ms],
Range 1...50 ms, Default: 0 ms
DO.LS/LB Interval
WORD
W
Period [s] required for line diagnosis
Range 1…100 s, 1 s steps
DO[XX].LS
Monitoring with
red. Voltage
BOOL
W
Line diagnosis with reduced voltage
Coding
Description
FALSE
Normal signal voltage level
TRUE
Reduced signal voltage level
(Reduced signal voltage level only at DO[xx].LSLB
Monitoring = 1 effective!)