F3 DIO 16/8 01
4 Start-Up
HI 800 177 E Rev. 1.01
Page 33 of 58
4.2 Configuration
The remote I/O can be configured using a programming tool, SILworX or ELOP II Factory.
Which programming tool should be used depends on the revision status of the operating
system (firmware):
ELOP II Factory is required for operating system versions prior to 7.
SILworX is required for operating system version 7 and beyond.
i
ELOP II Factory is required to load a new operating system (version 7 and beyond) into a
remote I/O with a CPU operating system version prior to 7. SILworX is then required once
the loading procedure is completed.
4.3
Configuring the Remote I/O with SILworX
In the Hardware Editor, the remote I/Os are represented like a base plate equipped with the
following modules:
Processor module (CPU)
Input module (DI 16 LC) with Line Control
Output module (DO 8 03)
Pulsed module (DO 2 01) with 2 outputs
Double-click the module to open the Detail View with the corresponding tabs. The tabs are
used to assign the global variables configured in the user program to the system parameter
of the corresponding module.
4.3.1
Parameters and Error Codes for the Inputs and Outputs
The following tables specify the system parameters that can be read and set for the inputs
and outputs, including the corresponding error codes.
In the user program, the error codes can be read using the variables assigned within the
logic.
The error codes can also be displayed in SILworX.
4.3.2
Digital Inputs of F3 DIO 16/8 01
The following tables present the statuses and parameters for the input module (DI 16 LC) in
the same order as given in the Hardware Editor.