HIMA HIMatrix F2 DO 16 01 Product Description Download Page 1

HIMatrix 

Safety-Related Controller 

F2 DO 16 01 Manual 

 

 

 

 

HIMA Paul Hildebrandt GmbH + Co KG 

Industrial Automation 

Rev.  1.01 

HI 800 159 E

Summary of Contents for HIMatrix F2 DO 16 01

Page 1: ...HIMatrix Safety Related Controller F2 DO 16 01 Manual HIMA Paul Hildebrandt GmbH Co KG Industrial Automation Rev 1 01 HI 800 159 E...

Page 2: ...n on which information should be included in the manual Equipment subject to change without notice HIMA also reserves the right to modify the written material without prior notice For further informat...

Page 3: ...Information 10 3 Product Description 11 3 1 Safety Function 11 3 1 1 Safety Related Digital Outputs 11 3 1 1 1 Reaction in the Event of a Fault 12 3 2 Equipment Scope of Delivery 13 3 2 1 IP Address...

Page 4: ...Module Tab 26 4 3 2 2 DO 16 Channels Tab 27 4 4 Configuring a Resource Using ELOP II Factory 27 4 4 1 Configuring the Outputs 27 4 4 2 Signals and Error Codes for the Output 27 4 4 3 Digital Outputs f...

Page 5: ...n Start Up Operation Maintenance Decommissioning Transport Disposal This manual distinguishes between the following variants of the HIMatrix system Programming tool Processor operating system SILworX...

Page 6: ...orX ELOP II Factory Online Help Instructions on how to use ELOP II Factory Ethernet IP protocol INTERBUS protocol First Steps SILworX Introduction to SILworX using the HIMax system as an example HI 80...

Page 7: ...larly marked 1 3 1 Safety Notes The safety notes are represented as described below These notes must absolutely be observed to reduce the risk to a minimum The content is structured as follows Signal...

Page 8: ...E Rev 1 01 1 3 2 Operating Tips Additional information is structured as presented in the following example i The text corresponding to the additional information is located here Useful tips and tricks...

Page 9: ...dance with IEC EN 61131 2 Ambient temperature 0 60 C Storage temperature 40 85 C Pollution Pollution degree II in accordance with IEC EN 61131 2 Altitude 2000 m Housing Standard IP20 Supply voltage 24...

Page 10: ...e user program Faults in the wiring 2 3 Safety Precautions Observe all local safety requirements and use the protective equipment required on site 2 4 Emergency Information A HIMatrix system is a part...

Page 11: ...IL 3 IEC 61508 IEC 61511 and IEC 62061 Cat 4 EN 954 1 and PL e EN ISO 13849 1 Further safety standards application standards and test standards are specified in the certificate available on the HIMA w...

Page 12: ...put is set to the initial value configured This effect must be taken into account for the behavior of the connected output If an overload occurs one or all outputs are switched off If the overload is...

Page 13: ...is delivered with the device to allow one to note the IP address and the system ID SRS for system rack slot after a change IP___ ___ ___ ___SRS____ __ __ Default value for IP address 192 168 0 99 Defa...

Page 14: ...Assembly This chapter describes the layout and function of the remote I O and its communication via safeethernet DO 16 01 2 Figure 3 Front View DO 1 DO 16 1 2 3 4 RJ 45 RJ 45 16 Digital Outputs Safet...

Page 15: ...es LEDs indicate the operating state of the remote I O The LEDs are classified as follows Operating voltage LED System LEDs Communication LEDs I O LEDs 3 4 1 1 Operating Voltage LED LED Color Status D...

Page 16: ...ted On A new configuration is being loaded into the device Blinking The device switches from INIT to STOP A new operating system is being loaded into the flash ROM PROG Yellow Off No configuration or...

Page 17: ...LED Status Description On Full duplex operation Blinking Collision Green Off Half duplex operation no collision On Connection available Blinking Interface activity Yellow Off No connection available...

Page 18: ...more information on the communication LEDs refer to Chapter 3 4 1 3 The connection parameters are read based on the MAC address media access control address defined during manufacturing The MAC addres...

Page 19: ...g material to avoid short circuits within the remote I O The reset is only effective if the remote I O is rebooted switched off and on while the key is simultaneously engaged for at least 20 seconds E...

Page 20: ...n IP20 Max dimensions without plug Width 207 mm with enclosure screws Height 114 mm with fixing bolt Depth 66 mm with earthing screw Weight 0 85 kg Table 11 Product Data Digital outputs Number of outp...

Page 21: ...X 94 9 EG EN 1127 1 EN 61508 UL Underwriters Laboratories Inc ANSI UL 508 NFPA 70 Industrial Control Equipment CSA C22 2 No 142 UL 1998 Software Programmable Components NFPA 79 Electrical Standard for...

Page 22: ...utput DO 3 5 4 Digital output DO 4 6 L Ground channel group D1 Terminal Designation Function outputs D1 below 13 L Ground channel group D1 14 9 Digital output DO 9 15 10 Digital output DO 10 16 11 Dig...

Page 23: ...rate operating voltages however both clamp terminal blocks must be connected A group s total current input must not exceed 9 A If a group exceeds the total current input it is switched off and then sw...

Page 24: ...er voltage 2 The enclosure in use must be able to safely dissipate the generated heat Depending on the output load and supply voltage the HIMatrix F2 DO 16 01 module has a power dissipation ranging be...

Page 25: ...LworX In the Hardware Editor the remote I O is represented as a device with the following modules Processor module CPU Output module DO 16 Double click the module to open the Detail View with the corr...

Page 26: ...0200 Outputs 5 8 and 13 16 de energized due to total current overrun 0x0400 FTT test 1st temperature threshold exceeded 0x0800 FTT test 2nd temperature threshold exceeded 0x1000 FTT test Monitoring of...

Page 27: ...gized Table 17 SILworX System Parameters for Digital Outputs DO 16 Channels Tab 4 4 Configuring a Resource Using ELOP II Factory 4 4 1 Configuring the Outputs The signals previously defined in the Sig...

Page 28: ...liary voltage returns a fault 0x0008 FTT test of test pattern faulty 0x0010 MOT test of output switch test pattern faulty 0x0020 MOT test of output switch test pattern shutdown test of the outputs fau...

Page 29: ...ether with a controller No specific monitoring is required for remote I Os 5 1 Handling Handling of the remote I O during operation is not required 5 2 Diagnosis A first diagnosis results from evaluat...

Page 30: ...42 If the test harnesses detect faults in the processor system the module automatically enters the ERROR STOP state and will remain in this state This means that the input signals are no longer proces...

Page 31: ...ning HI 800 159 E Rev 1 01 Page 31 of 40 7 Decommissioning Remove the supply voltage to decommission the device Afterwards pull out the pluggable screw terminal connector blocks for inputs and outputs...

Page 32: ...echanical damage HIMatrix components must be transported in packaging Always store HIMatrix components in their original product packaging This packaging also provides protection against electrostatic...

Page 33: ...age 33 of 40 9 Disposal Industrial customers are responsible for correctly disposing of decommissioned HIMatrix hardware Upon request a disposal agreement can be arranged with HIMA All materials must...

Page 34: ...9 Disposal F2 DO 16 01 Page 34 of 40 HI 800 159 E Rev 1 01...

Page 35: ...ctronic System PFD Probability of Failure on Demand probability of failure on demand of a safety function PFH Probability of Failure per Hour probability of a dangerous failure per hour R Read The sys...

Page 36: ...I 800 159 E Rev 1 01 Index of Figures Figure 1 Connection of Actuators to Outputs 11 Figure 2 Sample Type Label 13 Figure 3 Front View 14 Figure 4 Block Diagram 14 Figure 5 Sample MAC Address Label 18...

Page 37: ...LEDs 17 Table 9 Ethernet Interfaces Properties 18 Table 10 Network Ports in Use 18 Table 11 Product Data 20 Table 12 Specifications for the Digital Outputs 20 Table 13 Certified HIMatrix F2 DO 16 01...

Page 38: ...Appendix F2 DO 16 01 Page 38 of 40 HI 800 159 E Rev 1 01 Index diagnosis 30 fault reaction digital outputs 12 part number 13 safeethernet 19 SRS 13...

Page 39: ......

Page 40: ...1025 HIMA Paul Hildebrandt GmbH Co KG P O Box 1261 68777 Br hl Germany Tel 49 6202 709 0 Fax 49 6202 709 107 E mail info hima com Internet www hima com HI 800 159 E by HIMA Paul Hildebrandt GmbH Co KG...