DI 24 01
3 Product Description
HI 800 201 E Rev. 1.00
Page 15 of 34
3.4.3 Status
Indicators
LED
Color
Status
Description
On
Operating voltage present
RUN
Green
Off
No operating voltage
On
Module faulty or external faults
Reaction as dictated by the diagnosis
ERR
Red
Off
No module faults and / or no channel faults
Table 5:
Status Indicators
3.4.4 I/O
LEDs
LED
Color
Status
Description
On
The related channel is active (energized).
I1...I16
Yellow
Off
The related channel is inactive (de-energized).
Table 6:
I/O LEDs
3.5 Product
Data
General
Operating voltage
24 VDC, -15 %...+20 %, w
ss
≤
15 %,
provided by a power supply unit with safe isolation
in accordance with IEC 61131-2 requirements.
Operating data
3.3 VDC / 0.05 A
24 VDC / 0.1 A (High level = 79 V)
Ambient temperature
0 °C...+60 °C
Storage temperature
-40 °C...+85 °C
Space requirement
6 RU, 4 HP
Weight 260
g
Table 7:
Product Data
Digital inputs
Number of inputs
24 (galvanically isolated)
Input voltage
High
level
Low
level
110 VDC nom. 127 VAC (monophase)
≥
79 V
≤
20 V
Input current
High level
≥
2.2 mA at 79 V
Table 8:
Specifications for Digital Inputs
Summary of Contents for HIMatrix DI 24 01