Device drawings and connectors
35/75
5.7
Fieldbus interfaces (X3)
For identification, see position
(15)
Information on fieldbus cabling can be found in the user manual
Wiring Instructions,
DOC120208UMxxEN, stored on the netHOST
Solutions DVD in the Documentation\english\4.Installation
Instructions directory.
5.7.1
PROFIBUS DP interface (NHST-T100-DP/DPM)
The PROFIBUS DP interface at X3 is a RS-485 interface according to
PROFIBUS standard EN 50170.
PROFIBUS
Pin
Signal
Description
9-pole sub-D
socket, female
3
Rx/Tx +
Receive- / Transmit data positive
4
CNTR-P
Control signal for repeater (direction control)
5
ISO GND
Data ground
6
VP
Power supply positive 5V for terminating
resistor. Maximum current 100 mA.
8
Rx/Tx ‑
Receive- / Transmit data negative
Shield
PE
Metal shell on PE
Table 25: PROFIBUS RS-485 pin assignment
A pull up resistor of 100 kΩ is connected inside the device at “Rx / Tx +“.
A pull down resistor of 100 kΩ is connected inside the device at “Rx / Tx -“.
5.7.2
CANopen interface (NHST-T100-CO/COM)
The CANopen interface at X3 is an ISO 11898 interface according to the
CANopen CiA DS 102 standard.
CANopen
Pin
Signal
Description
9-pole
sub-D male
2
CAN L
CAN Low bus line
3
ISO GND
CAN ground
7
CAN H
CAN High bus line
1, 4, 5,
6, 8, 9
Important note and strongly recommended:
Leave these pins unconnected! Otherwise there
is a high risk of a device damage.
Shield
PE
Metal shell on PE
Table 26: CANopen pin assignment
netHOST NHST-T100 | LAN controlled master devices
DOC130401UM05EN | Revision 5 | English | 2018-05 | Released | Public
© Hilscher 2013 – 2018