Technical Data
245/299
PC Cards cifX Compact PCI, Mini PCI, Mini PCIe, PCI-104 | Installation, Operation and Hardware Description
DOC120205UM53EN | Revision 53 | English | 2019-03 | Released | Public
© Hilscher, 2008-2019
Parameter
Description
Limitations
The size of the bus configuration file is limited by the size of the RAM
Disk (1 Mbyte)
The usable (minimum) cycle time depends on the number of used IO
Devices, the number of used input and output data.
RT over UDP not supported
Multicast communication not supported
DHCP is not supported (neither for PROFINET IO Controller nor for
IO-Devices)
Only one IOCR per IO-Device per direction
One instance of DeviceAccess AR can be used at the same time only
MRPD is not supported
Planning of IRT is not done by the PROFINET IO Controller protocol
stack
Sync Slave is not supported
One fragmented acyclic services can be used at the same time only
Multiple MRP Managers are not supported
One DCP Service can be used in parallel only
Multiple Sync Masters are not supported
Reference to firmware / stack version
V3.3
Table 179: Technical Data PROFINET IO Controller Protocol
10.4.12 PROFINET IO-Device (V3.4)
Parameter
Description
Maximum number of cyclic input data
1024 bytes
Maximum number of cyclic output data
1024 bytes
Acyclic communication
Read/Write Record, max. 1024 bytes per telegram
Alarm Types
Process Alarm, Diagnostic Alarm, Return of SubModule Alarm
Plug Alarm (implicit), Pull Alarm (implicit)
Supported protocols
RTC – Real Time Cyclic Protocol, Class 1 and 2 (unsynchronized), Class
3 (synchronized)
RTA – Real Time Acyclic Protocol
DCP – Discovery and configuration Protocol
CL-RPC – Connectionless Remote Procedure Call
LLDP – Link Layer Discovery Protocol
SNMP – Simple Network Management Protocol
MRP – MRP Client
Used Protocols (subset)
UDP, IP, ARP, ICMP (Ping)
Topology recognition
LLDP, SNMP V1, MIB2, physical device
VLAN- and priority tagging
yes
Context Management by CL-RPC
Supported
Identification & Maintenance
Read and write of I&M1-4
Minimum cycle time
1 ms for RTC1 and RTC2
250 µs for RTC3
Baud rate
100 MBit/s
Data transport layer
Ethernet II, IEEE 802.3
Limitations
RT over UDP not supported
Multicast communication not supported
Only one device instance is supported