4.5 Configure Linkage Actions
Alarm linkage actions will be activated when an alarm or exception occurs, including Event Hint
Display, Full Screen Monitoring, Audible Warning (buzzer), Notify Surveillance Center, Trigger Alarm
Output, and Send Email.
4.5.1 Configure Auto-Switch Full Screen Monitoring
When an alarm is triggered, the local monitor displays in full screen the video image from the
alarming channel configured for full screen monitoring. And when the alarm is triggered
simultaneously in several channels, you must configure the auto-switch dwell time.
Note
Auto-switch will terminate once the alarm stops and back to the live view interface.
Steps
1. Go to System → View → General .
2. Set the event output and dwell time.
Event Output
Select the output to show the event video.
Full Screen Monitoring Dwell Time
Set the time in seconds to show the alarm event screen. If alarms are triggered
simultaneously in several channels, their full-screen images will be switched at an interval of
10 seconds (default dwell time).
3. Go to the Linkage Action interface of the alarm detection (e.g., motion detection, video
tampering, face detection, etc.).
4. Select the Full Screen Monitoring alarm linkage action.
5. Select the channel(s) in Trigger Channel for full screen monitoring.
4.5.2 Configure Audio Warning
The audio warning has the system to trigger an audible beep when an alarm is detected.
Steps
1. Go to System → View → General .
2. Enable the audio output and set the volume.
3. Go to Linkage Action interface of the alarm detection (e.g., motion detection, video tampering,
face detection, etc.).
4. Select the Audio Warning alarm linkage action.
ATM Digital Video Recorder User Manual