INSTALLATION, MAINTENANCE AND USER'S GUIDE

FAN WITH ELECTRONICALLY COMMUTATED EXTERNAL-ROTOR MOTOR

Fan Code:

0314-4-0089

Fan type : R14R-56APS-ET60B-03B18

&

Note :

Table of Contents :

01

SAFETY

02

TYPICAL FEATURES AND PROPER USE

03

OPERATING CONDITIONS

04

INSTALLATION AND CONNECTION

05

SPEED CONTROL

06

PUTTING INTO OPERATION

07

DIAGNOSTICS & TROUBLESHOOTING

08

PROTECTIVE FEATURES

09

MAINTENANCE, SERVICE AND CLEANING

10

TRANSPORT AND STORAGE

11

ErP, ROHS AND EMC DIRECTIVES

12

SERVICE ADDRESSES AND ADDITIONAL DATA

Be sure to familiarize yourself with these instructions before working on this unit. Not paying attention to these warnings
and instructions may lead to malfunctions and failures or may seriously endanger human life.

Symbols :

WARNING - to indicate warning situation 

NOTE - indicate valuable information

Summary of Contents for 0314-4-0089

Page 1: ...G INTO OPERATION 07 DIAGNOSTICS TROUBLESHOOTING 08 PROTECTIVE FEATURES 09 MAINTENANCE SERVICE AND CLEANING 10 TRANSPORT AND STORAGE 11 ErP ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL D...

Page 2: ...dental contact according to machinery directive 2006 42 CE has to be safeguarded especially for the rotating parts Should there be a malfunction it still has to be safeguarded that the parts breaking...

Page 3: ...nce is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanen...

Page 4: ...fes 50 2 Installation category A Efficiency category static Efficiency grade N 57 8 Variable speed drive INTEGRATED Power Input Pelec 630 1 W Airflow volume qV 6608 m h Pressure Increase ps 160 Pa Rot...

Page 5: ...onnection must correspond to the enclosed connection diagram Recommended cable for power supply and alarm relay contact is an ordinary PVC cable acc to IEC 60227 5 eg H05V2V2 F 4G 1 mm no longer than...

Page 6: ...A RS B 0 10V analog input 0 10V GND 4 20mA analog input 4 20mA GND Sensor supply 10V GND or 20V GND Slave control OUT GND The device is compatible with Modbus protocol RTU Please read additional inst...

Page 7: ...g a pressure sensor 0 20Bar 0 10V but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at...

Page 8: ...pply voltage inadequate control signal or fan overheating Check line voltage check control signal check temperature and sufficient airflow of cooling air or loss of motor cooling Attention In the even...

Page 9: ...orce for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans i...