rev 10 – USER MANUAL
RS
Dehumidifiers for radiant systems
16 - 52
6
TECHNICAL DATA
6.1
TECHNICAL DATA TABLES
6.1.1
Size 020
Horizontals
Verticals
RSO
RSE
RSV
RSVE
A
I
A
I
A
I
A
I
Dehumidification capacity
l/day
20
20
20
20
20
20
20
20
Refrigerant
-
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
Cooling capacity
W
/
1240
/
1240
/
1240
/
1240
Absorbed power
W
250
250
240
240
250
250
240
240
Absorbed current
A
1,7
1,7
1,8
1,8
1,7
1,7
1,8
1,8
Electrical supply
V/ph/Hz
230 / 1+N / 50
230 / 1+N / 50
230 / 1+N / 50
230 / 1+N / 50
Airflow
m³/h
250
250
250
250
250
250
250
250
Available static pressure
Pa
40
40
180
180
40
40
180
180
Nominal water flow
l/h
150
150
150
150
150
150
150
150
Water pressure drop
kPa
15
15
15
15
15
15
15
15
Storing temp. limit
°C
-10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43
Storing humidity limit
%
90
90
90
90
90
90
90
90
Sound pressure level
dB(A)
38
38
39
39
38
38
39
39
Dimensions
mm
530x600x242
530x600x242
480x220x665
480x220x665
Weight
kg
35
37
35
37
34
36
34
36
6.1.2
Size 035
Horizontals
Verticals
RSO
RSE
RSV
RSVE
A
I
A
I
A
I
A
I
Dehumidification capacity
l/day
28
28
28
28
28
28
28
28
Refrigerant
-
R134a
R134a
R134a
R134a
R134a
R134a
R134a
R134a
Cooling capacity
W
/
1740
/
1740
/
1740
/
1740
Absorbed power
W
800
800
780
780
800
800
780
780
Absorbed current
A
4,8
4,8
4,9
4,9
4,8
4,8
4,9
4,9
Electrical supply
V/ph/Hz
230 / 1+N / 50
230 / 1+N / 50
230 / 1+N / 50
230 / 1+N / 50
Airflow
m³/h
350
350
350
350
350
350
350
350
Available static pressure
Pa
40
40
180
180
40
40
180
180
Nominal water flow
l/h
260
260
260
260
260
260
260
260
Water pressure drop
kPa
18
18
18
18
18
18
18
18
Storing temp. limit
°C
-10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43 -10 / +43
Storing humidity limit
%
90
90
90
90
90
90
90
90
Sound pressure level
dB(A)
39
39
40
40
39
39
40
40
Dimensions
mm
680x600x242
680x600x242
630x220x665
630x220x665
Weight
kg
42
44
42
44
41
43
41
43
Units “I” need to be supplied with cold water in order to function properly, otherwise units cannot
function and they will block.
Units “A” can function without cold water, in this case dehumidification capacity decrease and air is supplied at temperature higher
than the inlet.
1.
Dehumidification capacity is declared at nominal conditions 26°C, 65% RH with water at 15°C.
In other conditions dehumidification capacity varies.
2.
Sound pressure level is declared in free field at 1 m from the unit ducted.