VertX EVO series

Before being able to directly connect the device to CredoID software, network and user settings of the HID devices have to be configured through 
their graphical user interface. Have the device powered up and Ethernet cable connected to the network/system.

Open a web browser and enter the HID devices IP. By default, every HID controller is configured to respond to a fixed IP address, that is 
169.254.242.121. Be sure that your network settings are configured correctly to be able to connect to the controller.
You should be greeted with a login screen. If connecting to the controller for the first time, in the User name field, enter "admin" and leave 
the password field empty. If not, enter a configured password.
After authentication is done, you should be presented with Basic setup information window, where network and other settings can be 
configured. It is highly recommended to configure a static IP address, for more stable connection. After configuring network settings, set up a 
password, if you haven't yet done that and set "Here I am interval" to 120 seconds. After all settings have been configured and saved, closed 
down the window.

Tamper, AC Fail, Batt Fail values

To change default HID values of monitoring inputs follow these steps:

After logging into the controller, click "Supplemental Configuration".
Click device or module of which default input state needs to be changed
Use the table below for default ADC values or adjust according to installation requirements.

Device

Default 
state

HRUL

HRLL

LRUL

LRLL

V1000

N/C

128

0

128

0

N/O

255

128

255

128