background image

HID Mercury™ LP4502 Controller 

Installation and Specifications

 

 

PLT-05246, A.4
June 2021

HID Mercury™ LP4502 Controller  Installation and Specifications

 

Powering

Trusted Identities

Summary of Contents for Mercury LP4502

Page 1: ...HID Mercury LP4502 Controller Installation and Specifications PLT 05246 A 4 June 2021 HID Mercury LP4502 Controller Installation and Specifications Powering Trusted Identities...

Page 2: ...chnical Support www hidglobal com support Americas and Corporate Asia Pacific 611 Center Ridge Drive Austin TX 78753 USA Phone 1 866 607 7339 19 F 625 King s Road North Point Island East Hong Kong Pho...

Page 3: ...Section 01 Powering Trusted Identities Overview...

Page 4: ...he LP4502 Each reader port can accommodate a read head that utilizes TTL D1 D0 Clock Data F 2F or 2 wire RS 485 electrical signaling OSDP reader for example and also provides tri state LED control and...

Page 5: ...1 2 LP4502 hardware PLT 05246 A 4 5 June 2021 Powering Trusted Identities HID Mercury LP4502 Controller Installation and Specifications...

Page 6: ...Section 02 Powering Trusted Identities LP4502 wiring and setup...

Page 7: ...B 1 TB3 1 GND SIO port 2 2 wire RS 485 TB3 2 TR A 1 TB3 3 TR B 1 TB4 1 IN2 Input 2 TB4 2 IN2 TB4 3 IN1 Input 1 TB4 4 IN1 TB5 1 IN4 Input 4 TB5 2 IN4 TB5 3 IN3 Input 3 TB5 4 IN3 TB6 1 IN6 Input 6 TB6 2...

Page 8: ...O Out 1 Normally open contact TB10 2 C Out 1 Common TB10 3 NC Out 1 Normally closed contact TB10 4 NO Out 2 Normally open contact TB10 5 C Out 2 Common contact TB10 6 NC Out 2 Normally closed contact...

Page 9: ...D card J9 OFF Port 1 RS 485 EOL terminator is OFF ON Port 1 RS 485 EOL terminator is ON J10 1 N A Remote Status LED 1 1 J10 2 N A Remote Status LED 2 1 J10 3 N A Remote Status LED 3 1 J10 4 N A Remote...

Page 10: ...OFF Bulk Erase prompt mode at power up See Bulk erase configuration memory X X X ON Makes the LP4502 report and function like an EP4502 To be used in situations where the host software has not been up...

Page 11: ...D 1 is on for about 15 seconds while LP4502 boots up 3 Change DIP switches 1 or 2 to OFF Within 10 seconds after LEDs 1 and 2 and LEDs 3 and 4 start flashing alternately at a rate of 0 5 seconds If th...

Page 12: ...he host via the on board Ethernet 10 BaseT 100Base TX port and or the Micro USB port 2 0 with an optional Micro USB to Ethernet adapter The serial I O device communication ports TB2 for port 1 and TB3...

Page 13: ...485 signaling requires two 2 conductor cables Use one cable for power 18 AWG 1 pair and one cable for communication 24 AWG 1 pair shielded Note For OSDP cable lengths greater than 200 ft 61 m or EMF...

Page 14: ...er 2 OSDP installation Typical reader 2 Wiegand or Clock Data installation Typical unsupervised F 2F reader Typical supervised F 2F reader Jumper D1 to LED on supervised F 2F reader PLT 05246 A 4 14 J...

Page 15: ...voltage A supervised input circuit requires two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k 1 resistors and should be located as close...

Page 16: ...ded that a diode is used to protect the relay Wire should be of sufficient gauge to avoid voltage loss Diode selection n Diode current rating 1x strike current n Diode breakdown voltage 4x strike volt...

Page 17: ...On line 80 ON Double flash if battery is low 2 Host communication activity Ethernet 3 Internal SIO communication activity 4 External SIO communication activity Port 1 5 External SIO communication act...

Page 18: ...ith a default login account which is enabled when DIP 1 is moved from OFF to ON See DIP switches The default login user name admin and password password will be available for five minutes once the DIP...

Page 19: ...Section 03 Powering Trusted Identities Specifications...

Page 20: ...ormally closed contact NC 3 A 30 V DC resistive Reader interface Power jumper selectable 12 V DC 10 regulated 300 mA maximum each reader input voltage VIN must be greater than 20 V DC or 12 to 24 V DC...

Page 21: ...rranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Autho...

Page 22: ...t table in 2 6 Reader wiring A 3 February 2021 Correction to LP4502 connections A 2 January 2021 Add J19 Battery backup call out to the hardware diagram A 1 October 2020 Initial release A 0 PLT 05246...

Page 23: ...a Pacific 19 F 625 King s Road North Point Island East Hong Kong Europe Middle East Africa 3 Cae Gwyrdd Green Meadow Springs Cardiff CF15 7AB United Kingdom Brazil Condom nio Business Center Av Ermano...