HID Aero™ X100 Installation Guide

PLT-04234, Rev. A.3

6

Powering

Trusted Identities

LED

POWER 

ON SELF-TEST

NORMAL OPERATION

ONLINE

ON then OFF

Heartbeat and Online status. Offline = 1 sec rate, 20% ON. Online encrypted comm .1 sec 

ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .3 sec OFF. Waiting 

for application download .1 sec ON, .1 sec OFF.

COMM

ON then OFF

RS-485 Comm status. Indicates communication activity on the SIO communication port.

BATT FAIL

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

AC FAIL

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

TAMPER

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

IN 1

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

IN 2

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

IN 3

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

IN 4

ON then OFF

OFF = Inactive, ON = Active, Flash = Fault.*

READER 1

ON then OFF

Wiegand or C&D mode = Flashes when data is received, either input.  
OSDP mode = Flashes when transmitting data.

READER 2

ON then OFF

Wiegand or C&D mode = Flashes when data is received, either input.  
OSDP mode = Flashes when transmitting data.

RELAY 1

OFF

ON = Energized

RELAY 2

OFF

ON = Energized

RELAY 3

OFF

ON = Energized

RELAY 4

OFF

ON = Energized

*

If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 seconds, otherwise,  

the LED is OFF.

Status LEDs

7. 

Input power, cabinet tamper, and UPS fault input wiring

The X100 requires 12-24 V DC power. Connect power 

with minimum of 18 AWG wire. 

Grounding and Bonding: The DC ground or return wire 

must be bonded to the Earth Ground of the building, 

during installation.

Connect the power ground to earth ground in only ONE 

LOCATION within the system. Multiple earth ground 

connections may cause ground loop problems and is 

not advised.

Observe POLARITY on 12-24 V DC input.

Connect the 

AC FAIL

 and 

BATT FAIL

 inputs to the 

corresponding contacts provided on the power supply. 
Connect the 

TAMPER

 input to a tamper switch on the 

enclosure.

TAMPER

AC FAIL

, and 

BATT FAIL

 connections are 

identical to inputs 

IN 1

 to 

IN 4

 and can be configured 

as unsupervised or supervised. 

See step 4. Input circuit 

wiring

.

Summary of Contents for Aero X100

Page 1: ...ied DC power supply Drill with various bits for mounting hardware For DIN rail mounting Brackets 2 Phoenix Contact USA 10 Series Rail Adapter part number 1201578 Screws 4 Self tapping countersunk 3 0...

Page 2: ...ices on the bus To other devices on the bus 1 Mounting the X100 2 Communication wiring Connect the X100 to the Aero X1100 intelligent controller using IO Module ports 2 wire RS 485 Use 1 twisted pair...

Page 3: ...d separately Refer to the reader manufacture specifications for cabling requirements Note For OSDP cable lengths greater than 200 ft 61 m or EMF interference install 120 2 resistor across RS 485 termi...

Page 4: ...rm signaling When controlling the delivery of power to the door strike the NO Normally Open and C Common poles are typically used When momentarily removing power to unlock the door as with a mag lock...

Page 5: ...OFF OFF ON OFF Address 9 OFF ON OFF ON OFF Address 10 ON ON OFF ON OFF Address 11 OFF OFF ON ON OFF Address 12 ON OFF ON ON OFF Address 13 OFF ON ON ON OFF Address 14 ON ON ON ON OFF Address 15 OFF O...

Page 6: ...READER 2 ON then OFF Wiegand or C D mode Flashes when data is received either input OSDP mode Flashes when transmitting data RELAY 1 OFF ON Energized RELAY 2 OFF ON Energized RELAY 3 OFF ON Energized...

Page 7: ...dry contacts Normally open contact NO 5 A 30 V DC resistive Normally closed contact NC 3 A 30 V DC resistive READER INTERFACE Power 12 V DC 10 500 mA maximum each reader Data Inputs TTL compatible or...

Page 8: ...INE SECURITY LEVEL DESTRUCTIVE ATTACK LEVEL ENDURANCE LEVEL STAND BY POWER LEVEL CONDITIONS X100 Level I Level I Level IV Level I US FCC Class A Digital Devices FCC Compliance Statement This equipment...

Reviews: