HID Aero™ X100 Installation Guide
PLT-04234, Rev. A.3
6
Powering
Trusted Identities
LED
POWER
ON SELF-TEST
NORMAL OPERATION
ONLINE
ON then OFF
Heartbeat and Online status. Offline = 1 sec rate, 20% ON. Online encrypted comm .1 sec
ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .1 sec OFF, .1 sec ON, .3 sec OFF. Waiting
for application download .1 sec ON, .1 sec OFF.
COMM
ON then OFF
RS-485 Comm status. Indicates communication activity on the SIO communication port.
BATT FAIL
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
AC FAIL
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
TAMPER
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
IN 1
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
IN 2
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
IN 3
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
IN 4
ON then OFF
OFF = Inactive, ON = Active, Flash = Fault.*
READER 1
ON then OFF
Wiegand or C&D mode = Flashes when data is received, either input.
OSDP mode = Flashes when transmitting data.
READER 2
ON then OFF
Wiegand or C&D mode = Flashes when data is received, either input.
OSDP mode = Flashes when transmitting data.
RELAY 1
OFF
ON = Energized
RELAY 2
OFF
ON = Energized
RELAY 3
OFF
ON = Energized
RELAY 4
OFF
ON = Energized
*
If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 seconds, otherwise,
the LED is OFF.
Status LEDs
7.
Input power, cabinet tamper, and UPS fault input wiring
The X100 requires 12-24 V DC power. Connect power
with minimum of 18 AWG wire.
Grounding and Bonding: The DC ground or return wire
must be bonded to the Earth Ground of the building,
during installation.
Connect the power ground to earth ground in only ONE
LOCATION within the system. Multiple earth ground
connections may cause ground loop problems and is
not advised.
Observe POLARITY on 12-24 V DC input.
Connect the
AC FAIL
and
BATT FAIL
inputs to the
corresponding contacts provided on the power supply.
Connect the
TAMPER
input to a tamper switch on the
enclosure.
TAMPER
,
AC FAIL
, and
BATT FAIL
connections are
identical to inputs
IN 1
to
IN 4
and can be configured
as unsupervised or supervised.