FRU Replacement Guide
7 Storage Enclosure Basic Field Replaceable Units
78
b) Select the desired Storage Node.
Figure 48: A Storage Node Pane in the CMC
c) In the
Commands
pane, click
Shutdown
.
Figure 49: The Shutdown Button in the Commands Pane
d) Wait for the
Status
field to change to
DONE
.
Warning:
Even if all LEDs are off, you must still wait until the CMC shows
DONE
in the
Status
field.
All I/O to the Storage Enclosure Basic attached to this Storage Node is now quiesced.
6.
Go to the rack and identify the correct chassis by the blinking blue LED on its front and back panels.
7.
Locate the enclosure that contains the failed hard disk drive.
Note:
The enclosure containing the failed drive will have a flashing blue identification LED.
8.
Unplug the power cables by lifting the
power cord retention bale
and carefully removing the power cord from the
power supply
.