Description
Chassis
Fan
configuration
Number of drives
supported by the
server
Maximum inlet
ambient temperature
Apollo r2800
Gen10 Chassis
(24 SFF backplane
with SAS
expander)
Redundant and
nonredundant
0 to 24 drives
19°C (66.2°F)
Apollo r2800
Gen10 Chassis
(16 NVMe
backplane)
Redundant and
nonredundant
0 to 8 drives
22°C (71°F)
The drive capacity must be less than 10 TB.
The drive capacity must be greater than or equal to 10 TB.
If the component is installed in server 1, and the server is installed in the Apollo r2200 Gen10 Chassis, drive blanks
must be installed in drive bays 1-2 and 1-10. Similarly, if the component is installed in server 3, and the server is
installed in the Apollo r2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and 3-10. For more
information, see
Installing drive blanks and thermal bezel blanks for components with thermal limitations
on
page 23.
If NVIDIA Tesla M10 Quad GPUs are installed in the server, and the server is installed in the Apollo r2200 Gen10
Chassis, the maximum inlet ambient temperature can be increased by installing drive blanks in specific drive bays.
For more information, see
Installing drive blanks and thermal bezel blanks for components with thermal
If NVIDIA Tesla P4 GPUs are installed in the server, and the server is installed in the Apollo r2200 Gen10 Chassis,
the maximum inlet ambient temperature can be increased by installing drive blanks in specific drive bays. For more
information, see
Installing drive blanks and thermal bezel blanks for components with thermal limitations
on
page 23.
If NVIDIA Tesla P40 GPUs are installed in the server, and the server is installed in the Apollo r2200 Gen10 Chassis,
the drive blanks must be installed in specific drive bays. For more information, see
thermal bezel blanks for components with thermal limitations
on page 23.
To ensure proper thermal cooling with NVIDIA Tesla P100 GPUs or NVIDIA Tesla V100 GPUs installed in the server.
The server must be installed in the Apollo r2200 Gen10 Chassis or the Apollo r2600 Gen10 Chassis. The thermal
bezel blanks must also be installed in specific drive bays. For more information, see
thermal bezel blanks for components with thermal limitations
on page 23.
If the component is installed in server 1 and the server is installed in the Apollo r2200 Gen10 Chassis, bezel blanks
must be installed in drive bays 1-9, 1-10 and 1-11. If the component is installed in server 3 and the server is installed
in the Apollo r2200 Gen10 Chassis, bezel blanks must be installed in drive bays 3-9, 3-10 and 3-11. For more
information, see
Installing drive blanks and thermal bezel blanks for components with thermal limitations
on
page 23.
If the component is installed in server 1 and the server is installed in the Apollo r2600 Gen10 Chassis, bezel blanks
must be installed in drive bays 1-9 to 1-14. If the component is installed in server 3 and the server is installed in the
Apollo r2600 Gen10 Chassis, bezel blanks must be installed in drive bays 3-9 to 3-14. For more information, see
Installing drive blanks and thermal bezel blanks for components with thermal limitations
on page 23.
If the component is installed in server 1 and the server is installed in the Apollo r2800 Gen10 Chassis, the removable
blanks must be installed in drive bays 2-1 to 2-4. If the component is installed in server 3 and the server is installed in
the Apollo r2800 Gen10 Chassis, the removable blanks must be installed in drive bays 4-1 to 4-4. For more
information, see
Installing drive blanks and thermal bezel blanks for components with thermal limitations
on
page 23.
Specifications
157