• Extended overload
• Over temperature
• Output short
• Hardware failure
Configuring the UPS
Use the UPS front panel controls to configure the UPS.
IMPORTANT:
The output voltage of the UPS must be set to the same nominal voltage as the facility
input. Failure to do so will cause the UPS to buck or boost constantly to maintain the output voltage.
Changing the language
Procedure
1.
Press the
Enter
button to activate the menu options.
2.
Press the down arrow button until the Settings menu appears on the LCD menu screen.
3.
Press the
Enter
button.
4.
Press the down arrow button until the Local settings menu appears on the LCD menu screen.
5.
Press the
Enter
button.
6.
Press the down arrow button until the Language menu appears on the LCD menu screen.
7.
Press the
Enter
button.
8.
Press and hold the
Enter
button to change the language on the UPS.
Changing display functions
The control panel automatically dims after a long period of inactivity. Press any button to restore the
screen.
Press the
Enter
button to activate the menu options. Use the up and down arrow buttons to scroll through
the menu structure. Press the
Enter
button to enter a submenu or to select an option. Press the
ESC
button to cancel or return to the previous menu.
Menu map for display functions
Main menu
Submenu
Display information or menu function
Measurements —
Load, Input/Bypass voltage, Output/Efficiency voltage, Battery
percentage, Average power usage, Cumulative power usage
Control
Go to Bypass
Transfers the UPS on Bypass mode
Start battery
test
Starts a manual battery test
Reset fault state Clears active fault
Table Continued
26
Operations