HE 5731 Operating instructions
29
# 373344, Version 1.5
Parameterisation
7.2. Parameter table
Parameter
Adjustment range
Default
setting
Pre-assignment
Password
3-digit number that must be
entered before parameters
can be changed.
0 = no password protection
0…999
000
001
Pulse time
0
.01…9.99 s
0.10 s
0.10 s
Break time
1.0 s …999 s
5.0 s
5.0 s
Number of valves
1…64
16
16
Post-cleaning cycles
OFF, 1-20
1
1
Type of cleaning
Part/overall cycles
(0 = part cycle, 1-9 = over-
all cycle)
0…9
0
0
p-measuring range
(MB)
5.0…500 mbar
5.0 mbar
0…35 mbar
5…35 mbar
35 mbar
35 mbar
0…90 mbar
5…90 mbar
35 mbar
90 mbar
0…450mbar
5…450 mbar
35 mbar
450 mbar
High alarm [mbar]
Threshold for the high
alarm message.
If exceeded, the relay con-
tact is closed
OFF,
0%…500.0 mbar
30.0 mbar
30.0 mbar
(at
0…35 mbar
measuring range)
80.0 mbar
(at
0…90 mbar
measuring range)
390.0 mbar
(at
0…450 mbar
measuring range)
Upper threshold [mbar]
If exceeded, dp-dependent
cleaning starts.
Start of the
p-cycle
0.0
…500.0 mbar
15.0 mbar
15.0 mbar
(at
0…35 mbar
measuring range)
40.0 mbar
(at
0…90 mbar
measuring range)
190.0 mbar
(at
0…450 mbar
measuring range)