3.4
Technical data
Technical data
Measuring range:
Maximum of 35 mbar (90 or 450 mbar on request)
Maximum differential
pressure:
160 mbar
Basic accuracy:
± 1% of final value
Temperature drift:
± 0.05% / K of final value
Hysteresis:
± 0.5% of final value
Intended use:
Differential Pressure Regulator with integrated Measuring Hose Clean-
ing used to control the cleaning of industrial filtration plants
Supply voltage:
100 – 240 VAC ±10%
24 VDC ±10%
Power consumption:
Max. 30 W
Display:
7-segment display, 3 digits, 14 mm high, red for differential pressure dis-
play, parameter values and alarm messages
LEDs:
7 LEDs for status indications
16 LEDs for differential pressure indications
Buttons:
PARA (ESC), UP, DOWN, ENTER, TEST
Analogue output:
4...20 mA
Galvanically isolated
Max. permissible load: 400 Ω
Digital inputs:
Start, post cleaning. Internally supplied by 24 VDC / 1 mA
Relay outputs:
1 change-over contact 250 VAC, 5 A as a combined operating and
fault indicator
1 NO contact 250 VAC, 5 A as a cleaning indicator
2 change-over contacts 250 VAC, 5 A as alarm indicators
Interfaces:
USB Device, Type B for reading and writing of parameters (USB / TTL
adapter required)
Creepage distances
and clearances:
Contamination Class 2
Over voltage Category II
EMV:
Interference emission: DIN EN 61000-6-4
Interference immunity: DIN EN 61000-6-2
Housing:
ABS (acrylonitrile-butadiene-styrene)
IP65 Protection Class
Dimensions: 200 mm × 150 mm × 100 mm (W × H × D)
Cable glands:
1 x M25 with multiple sealing insert for 4 liens with 6 mm diameter
1 x M20 for supply and communication
Electrical connections:
Power supply: rigid/flex cross-section 2.5 mm
2
; flex.: max. 1.5 mm
2
with wire end ferrule
Rest: rigid/flex cross-section 1.5 mm
2
; flex.: max. 0.75 mm
2
with
wire end ferrule