Terms and definitions
8
Betriebsanleitung_PS_10_60_Touch_Englisch_V1.3
71
Position
Term
Display- /
Setting value
Description
Figure 7.49
Room influence
Setting value
Factor for the influence of the room
temperature. This value is adjustable
between 0 and 10. The higher the value
selected, the more influence a difference
in the actual room temperature will have
on the calculation of the flow fixed
temperature.
Correction
Setting value
This value is adjustable between - 5 and
+ 5. This value multiplied by 2 (fixed
value) gives the influence on the flow
fixed temperature. Only possible in
Heating time mode, Continuous heating
and continuous lowering.
Kneeling influence
Setting value
Factor for the influence of the lowering
temperature. This value is adjustable
between 0 and 10. The higher the value
selected, the more influence the room
temperature will have on the calculation
of the flow fixed temperature.
End run
Setting value
Limit value for the outside temperature. If
the outside temperature drops below this
value, the pump will run constantly in
order to stop the system from freezing up.
(Setting range from - 10 to + 10)
Figure 7.50
Day
middle
switching
temperature
Setting value
The day middle switching temperature
already mentioned works as an average
value generator. This means that from
when it is first switched on, an internal
average temperature generator of the
external temperature starts up. This runs
continuously in the background. Should
the daytime average target temperature
that you have set be exceeded, this is an
indication for the control system that it
should be changed to the automatic
summer mode. Here all heating circuits
are deactivated and so no heat demand
can be made. This means that the higher
the value set for the day middle switching
temperature, the later the change-over to
summer mode will then be.
Temp. increase
Setting value
Adjusting the temperature increase for
the required temperature
Due to power loss you can adjust an
addition to the must temperature
winter/summer of the tank circuit
Outside temp. sensor
Setting value
Activation of outside temperature sensor
Balancing outside sensor
Setting value
Setting balancing for the outside sensor
Summary of Contents for pelletstar 10
Page 1: ...Operating instructions pelletstar 10 60 ...
Page 92: ...13 Notes 92 Betriebsanleitung_PS_10_60_Touch_Englisch_V1 3 13 NOTES ...
Page 93: ...Notes 13 Betriebsanleitung_PS_10_60_Touch_Englisch_V1 3 93 ...
Page 94: ...13 Notes 94 Betriebsanleitung_PS_10_60_Touch_Englisch_V1 3 ...