Menu navigation and adjustment values
9
75
No. Fault report
Cause of fault
Fault correction
064
CLOSE BFP
if BFP-Closed-Contact is not reached
Check BFP-motor
Check fuel temperature
Clean intermediate hopper level sensor
Check drive arm
✆
- contracting party
065
CONTACTS BFP
if both BFP-contacts are active at the
same time
✆
- contracting party
Carry out check BFP by specialist
personnel
066
IGNITION
if ignition does not occur within 15
minutes
Check fuel level
Check burning parameters, adjust as adapt
Check fuel level during firing
Check ignition element
067
FIRE OUT
if no combustion is detected
Check fuel level
Check burning parameters, adjust as adapt
Clean intermediate hopper level sensor
068
TEMP. CONTROL
Fuel storage room temperature
sensor has exceeded the maximum
permissible temperature
Check fuel storage room
Alarm fire brigade in case of fire
069
STL
Boiler temperature has exceeded the
maximum permissible boiler
temperature
Cool down boiler (< 75 °C)
Quit STL
070
LAMBDA FUEL
when Lambda material correction is at
upper or lower limit (30 minutes)
✆
- contracting party
071
LAMBDA FUEL
if lambda probe value does not
change
✆
- contracting party
073
LAMBDA-
CALIBRATION
if calibration out of range or if other
error occurs during calibration and
aborts
✆
- contracting party
076
Standard Fuels
if
1) Pre-filling / Ignition insert cannot be
performed because no fuel
2) Failure “FIRE OUT” occurs for the
second time within 2 hours.
3) during operation intermediate
hopper is not full despite power
reduction
Check fuel level
Check burning parameters, adjust as adapt
Clean intermediate hopper level sensor
077
Additional input
when digital input responds to
additional input
Check failure at additional input aggregate
078
NIVEAU LEVEL
Active intermediate hopper level
sensor; low fuel level at intermediate
hopper
Check fuel level
Check discharge system (motor, screw,
springs)
079
SUCTION SENSOR
if sensor always reports fully during
suction (no sensor change)
Check fuel level
Check discharge system (motor, )
080
MP-ROOM
DISCHARGE
if digital input MP room discharge
responding
Check discharge system (motor, screw,
springs) to debris
081
Rotation speed ID fan
Speed outside the limits for more than
10 seconds
Check connection rotation speed sensor
Check ID-fan
✆
- contracting party
082
GRATE CLEANING 1
Grate cleaning failure; motor
damaged; grate linkage damaged or
loosened; misaligned grate sensor
Check grate cleaning motor
Check grate linkage
Check grate cleaning end switch
✆
- contracting party
083
GRATE CLEANING 2
Failure grate cleaning; impossible to
close grate; grate got stuck; grate
linkage damaged or loosened
Remove debris
Check grate cleaning motor
Check grate linkage
Check grate cleaning end switch
✆
- contracting party
Summary of Contents for pelletfire 20/20
Page 1: ...OPERATING INSTRUCTIONS Log wood pellet heating system pelletfire 20 40 ...
Page 90: ...15 Annex 90 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Page 91: ...Annex 15 91 Hydraulic recommendation 2 ...
Page 92: ...15 Annex 92 15 2 Solar module Program 1 ...
Page 93: ...Annex 15 93 Program 2 ...
Page 94: ...15 Annex 94 Program 3 ...
Page 95: ...Annex 15 95 Program 4 ...
Page 96: ...15 Annex 96 Program 5 ...
Page 97: ...Annex 15 97 Program 6 ...
Page 98: ...16 Notes 98 16 NOTES ...
Page 99: ...Notes 16 99 ...