Operating conditions
18
gas temperature, the boiler will switch to normal
output control.
Flame monitoring
If the burning chamber temperature fluctuates
greatly during operation, the boiler will switch off.
Antifreeze
If the freezing protection operates, the back flow
bypass pump will switch on only if the boiler is in
operating mode “HEATING OFF” or “BURNER
STOP”. Otherwise (freezing protection disabled)
the boiler will start up and heat up to minimum
boiler temperature 65 °C.
Lambda control
The amount of material and the rotation speed of
the ID-fan are controlled by the lambda control.
The control is able to detect marginal deviations of
the fuel quality and induces a combustion
improvement. Therefore, it is not necessary to re-
set the combustion after the silo is filled.