Basic operation
6-10. Setting the Clear time
Key [7]
This is the clear time setting procedure. Once the preset time is reached, the clear function
allows the planned quantity/production actual to set into
“0” and makes restarting. For this
machine, [CL] key should be pressed or the power source should be turned on/off once a
day. However, if the clear time is set before the beginning of the working hour, continuous
operation is enabled. The clear time can be set up to 3 times in total.
①
Press [7] key.
②
Set the time at which you want to clear for the first time.
<e.g.>
To set it at 7:55, input [7] [5] and [5] in this order.
If you have inadvertently set a wrong data, press [CLR] key and input once again.
③
Press [ENT] to set the clear time.
The screen displays the clear time 2.
In the same manner as for the first time, set the second and third clear time.
*You can get off/back the input screen using [+] [-] key.
④
To terminate the setting, press [ENT] while input column is being blank to get back to the
normal screen.
*The clear time can be registered up to 3-time for a day (23-hour 59-min).
*For the clear time which is not used, input [00:00].
*For 0:00, input [24:00].
*When the Controller power source was turned off at the clear time registered, this function does
not work.
{7}CLR1
[**:**]
Input
[
:
]
[
*
]present data
{7}CLR1
[**:**]
Input
[
7:55]
[
*
]present data
{7}CLR2
[**:**]
Input
[
:
]
[
*
]present data