2.6 

 

Connection of the sauna heater to the mains 

 

The sauna heater must be connected to the mains by a qualified electrician and in compliance with current 
regulations.    The sauna heater is connected with a semi-permanent connection. Use H07RN-F (60245 IEC 66) 
cables or a corresponding type. Other output cables (signal lamp, electric heating toggle) must also adhere to 
these recommendations. Do not use PVC insulated cable as a connection cable for the sauna heater. 

A multipolar (e.g. 7-pole) cable is allowed, if the voltage is the same. In the absence of a separate control current 
fuse, the diameter of all cables must be the same, i.e. in accordance with the front fuse.  

The connecting box on the sauna wall should be located within the minimum safety clearance specified for the 
sauna heater. The maximum height for the connection box is 500 mm from the floor. See page 9. Figure 3  
Locating the connecting box for the connection cable in the sauna room 

If the connection box is located at over 500mm distance from the heater, the maximum height is 1000mm from 
the floor.. 

 

Power 

 
 
 
 

kW 

S

auna heater’s 

connection cable 

H07RN 

F/ 60245 

IEC 66 

mm² 

400-415V 3N~ 

Fuse 

 
 
 

 

Sauna heater’s 

connection cable 

H07RN 

F/ 60245 

IEC 66 

mm² 

230V 3~ 

Fuse 

 
 
 

 

Sauna heater’s 

connection cable 

H07RN 

F/ 60245  

IEC 66 

mm² 

230V-240V 1N~ / 2~ 

Fuse 

 
 
 

 

6,0 

5 x 1,5 

3 x 10 

4 x 2,5 

3 x 16 

3 x 6 

1 x 35 

9,0 

5 x 2,5 

3 x 16 

4 x 6 

3 x 25 

---------- 

-------- 

 

Table 2  Connection cable and fuses 
 
 

NOTE:

 Controlling the lights in the sauna with the circuit board is only possible with resistive loads (incandescent 

light bulbs). The circuit board relay cannot withstand capacitive loads (switched-mode power supply units). If the 
lighting fixtures in the sauna have transformers, for example LED or halogen lamps, the stove circuit board's relay 
control must be fitted with a separate relay or contactor for controlling the lights. 

Sauna heater insulation resistance:

  

The sauna heater heating elements may absorb moisture from air, e.g. during storage. This may cause leakage 
currents. The moisture will be gone after a few heating sessions. Do not connect the heater power supply through 
a ground fault interrupter. 

However, adhere to the effective electrical safety regulation when installing the sauna heater. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2.7  Electric heating toggle 

 

Electric heating toggle applies to homes with an electric heating system. 

 
Sauna heater has connections (marked N-55) for controlling the electric heating toggle. Connectors N-55 and the 
heating elements are simultaneously live (230V). The sauna heater thermostat also controls the heating toggle. In 
other words, home heating turns on once the sauna thermostat cuts power off the sauna heater. 
 

 
 

Installation and User Manual  

HELO Roxx premium

 

Remove the nut and the rubber grom-
met from the strain relief bushing. Make 
a vertical split in the spot where the 
lead-in rubber grommet aligns with the 
hole. Insert the control panel's and 
sensor OLET 31 cable through the 
strain relief bushing and insert the cable 
through the splitted holes. Tighten the 
strain relief bushing nipple.  

Summary of Contents for 1107-60-040517

Page 1: ...A HEATER 1107 60 040517 1107 90 040517 230V 240V 1N 2 230V 3 400V 415V 3N CONTROL PANEL 1601 31 RA 31 Trend 1601 33 RA 33 Premium Wifi 314 SKLT 72 3 A Installation and User Manual HELO Roxx Premium RE...

Page 2: ...2 12 Heating the sauna 11 2 13 Sauna heater stones 12 2 14 If the sauna heater will not heat up 12 2 15 Door switch 13 2 16 Principle image when RA 33 Premium is used as control panel 14 2 17 BWT tech...

Page 3: ...these elements may extend the pre heating period even though the sauna room is otherwise well insulated see page 4 section 1 Preparing for sauna heater installation 1 3 Operation of the sauna heater...

Page 4: ...should be enough room around the sauna heater controls for maintenance purposes Also a doorway can be considered as a maintenance area Only a single sauna heater is allowed per sauna room 2 1 Installa...

Page 5: ...edges A through the holes in the heater so that the ingoing part is turned upwards The wall mount B is attached to the wall so that the holes where the locking wedges are secured to are upwards The mo...

Page 6: ...nsor is installed on the sauna room wall no more than 500 mm from the ceiling Once the additional sensor has been connected to the circuit board it is automatically acti vated This means that the temp...

Page 7: ...bove the heater and in line with the centre line of the heater Do not install the sensor anywhere else 100 490 100 10 280 D 10 40 100 490 100 10 280 D 10 40 Sensor OLET 31 Sensor OLET 31 Sensor OLET 3...

Page 8: ...uses NOTE Controlling the lights in the sauna with the circuit board is only possible with resistive loads incandescent light bulbs The circuit board relay cannot withstand capacitive loads switched m...

Page 9: ...rs 3 and 4 of a RJ10 circuit board The recommended cable size is AWG 24 or 26 The maximum length of an AWG 24 cable is 200 m when using a Trend controller The maximum length of an AWG 26 cable is 130...

Page 10: ...k l mmityksen vuorottelu Alternering med elv rme Signal kontakt Signal contact Contac t du signal Signaalcontact Contacto se al 3 Saunavalo Bastu belysning Saunabeleuchtung Sauna light clairage du sau...

Page 11: ...THERMOSTAT IS LOCATED IN THE SAME ZONE 2 12 Heating the sauna Before turning the sauna heater on make sure the sauna room is suitable for taking a sauna bath When heated for the first time the sauna h...

Page 12: ...iled so that they cover the heating elements Do not however pile a large heap of stones on the heating elements For a sufficient amount of stones refer to Table 1 on page 6 Any small stones in the pac...

Page 13: ...r edge of the door at least 300 mm from the inner corner The switch part is installed on the door frame and the magnet is installed on the door The distance between the switch and the magnet is 18 mm...

Page 14: ...cuit board OLEA 103 1 Blue 2 White 3 Red 4 Yellow End stop return acknowledgement Adapter circuit board OLEA 103 RJ10 intermedia cable Heater Control panel RA 33 Premium Control panel RA 33 Premium Se...

Page 15: ...emoved every so often The stones surrounding the tank must be removed during cleaning so that the tank can be lifted more easily When the water is boiling the moisture levels in the sauna remain high...

Reviews: