![Helmholz 700-672-PNC01 Manual Download Page 14](http://html1.mh-extra.com/html/helmholz/700-672-pnc01/700-672-pnc01_manual_2122269014.webp)
PN/CAN Gateway, PROFINET/CANopen Slave | Version 2 | 1/26/2021
14
4.2
Wiring of the PN/CAN Gateway
4.2.1
Voltage supply
The PN/CAN Gateway is supplied with 24 V DC voltage via the 3-pin power supply plug.
4.2.2
CAN bus connection
Pin
CAN bus D-sub connector
1
-
2
CAN low
3
CAN GND
4
-
5
PE, Shield
6
-
7
CAN high
8
-
9
-
PN/CAN Gateway contains no terminating resistor for the CAN bus!
4.2.3
PROFINET connection
Pin
Signal
RJ45 plug PROFINET
Color
Wire pair
1
TD+
Transmission data +
Yellow
1
2
TD-
Transmission data -
Orange
1
3
RD+
Receive data +
White
2
4
-
-
-
-
5
-
-
-
-
6
RD-
Receive data -
Blue
2
7
-
-
-
-
8
-
-
-
-
4.2.4
USB interface
The service USB interface is only required for the firmware update and for diagnoses in the event of
support.