| 6. Project planning
6. Project planning
6.1 General
All specifications in the operating
manual of the smoke alarm shall
apply to project planning and the
respective assembly position of the
smoke alarms.
Determine the following aspects:
number of smoke alarms with
radio module
their assembly positions
Also comply with the following
additional aspects:
connection of max. 30 radio
smoke alarms per line
distance between 2 radio users:
min. 0.5 m, max. approx. 30 m
distance to external radio
systems (e.g. router, DECT
telephones, radio loudspeakers,
baby monitor ): min. 2 m
observe signal propagation
times ( see chapter "General
information")