Control unit for hold-open systems

FSZ Pro

Edition 19.09.2018

7003067

 

Instruction manual

Summary of Contents for FSZ Pro

Page 1: ...www hekatron de Control unit for hold open systems FSZ Pro Edition 19 09 2018 7003067 Instruction manual...

Page 2: ...2...

Page 3: ...FSZ Pro applications 13 9 Electrical Installation 14 9 1 Installation instruction 14 9 2 Control unit FSZ Pro for hold open systems 16 9 3 Termination module AM 142 19 9 4 FSZ Pro operation 20 9 5 Ho...

Page 4: ...ctional test 38 11 4 Annual testing and maintenance 38 11 5 Functional test 39 11 6 Maintenance 40 11 7 Obligatory documentation requirement 40 12 Annex 41 12 1 Order data 41 12 2 Drilling template 41...

Page 5: ...r changes to the equipment are not permitted The equipment must be used only for its intended purpose in an undamaged and perfect condition No other spare parts than those available from the manufactu...

Page 6: ...abelled T r schlie en Close door and Tor schlie en Close gate 1 x termination module AM 142 3 Warranty In case of non compliance with the information contained in this Instruction Manual any claims fo...

Page 7: ...an be switched on or off optionally Additional relay with a potential free alternating contact for free use Common features FSZ Pro and FSZ Basis Integrated manual release button conforming to standar...

Page 8: ...hing voltage DC Switching current at 30 V DC Switching current at 24 V DC 2 alternating contact potential free max 250 V AC max 5 A AC max 30 V DC max 3 A DC max 5 A DC Sound volume piezo internal typ...

Page 9: ...signal white according to RAL 9003 Installation exposed assembly Installation position as desired Cable entries 6 x M16 und 2 x M20 Dimensions HxWxD 146 mm x 146 mm x 60 5 mm Weight with without ESM P...

Page 10: ...425 2 x 63 mA 126 mA Total current requirements 192 mA The total current must not exceed 900 mA The current consumption of the various components of the hold open system is specified in the related pr...

Page 11: ...s as a guide for the groove in the printed circuit board of the ESM Pro Figure 2 Place the ESM Pro on the printed circuit board as shown Fig 2 Figure 3 Make sure that the contact pins Fig 3 are insert...

Page 12: ...d dowels The installation position can be selected as desired The FSZ accessories kit which must be ordered separately includes two mounting adapters for installation of the FSZ Pro in a switch cabine...

Page 13: ...be activated via DIP switch 3 EN 14637 One termination module AM 142 or a magnet for ORS 142 must each be connected in the last detector to be connected and in the manual button see Fig 7 resp Fig 8 I...

Page 14: ...cted with regard to electrical engineering An interrupter circuit breaker max 10 A tripping characteristic B must be installed in the supply circuit The place of installation of the interrupter must b...

Page 15: ...section of the power supply cord must not exceed 2 5 mm Hold open system wiring Recommended line type without smoke switch in combination with a smoke status indicator switch status indicator IY ST Y...

Page 16: ...nection terminals Connection of ext manual release and reset button Mains connection 230 V AC Potential free alternating contact Connection of smoke switch Terminal points Connection of hold open syst...

Page 17: ...potential free contact 3 Relay line voltage NO Closed when system in operation 24 V Output voltage 24 V DC GND Output voltage 0 V DC ORS Feedback from ORS alarm loop K Connection point terminal B Con...

Page 18: ...nce is switched off the inputs for the external manual button and the external alarm input must be bridged when not in use When line monitoring is switched on see pages 28 29 und 30 the input of the e...

Page 19: ...M 142 connection Coming from the power supply unit or the second to last smoke switch Going to the last smoke switch 24 V yellow feedback alarm loop GND white feedback alarm loop connected internally...

Page 20: ...t ohne Hupe with without horn O N 3 2 1 6 5 4 Fig 4 DIP switches for FSZ Pro configuration Alarm storage DIP 1 OFF The FSZ Pro does not store an incoming alarm If the releasing smoke switch resets its...

Page 21: ...Z Pro is used according to DIN EN 14637 this DIP switch must be set to ON If the FSZ Pro is used according to DIBt the system can be used with and without line surveillance Irrespective of the type of...

Page 22: ...itched off all relays are energised again the THM is energised and the fault LED and the piezo remain off The 24 V supply voltage is switched on again If the alarm storage is switched on all relays an...

Page 23: ...rm storage function is switched on a manual reset must always be carried out after the mains voltage returns regardless of during discharging the ESM Pro or after discharging the ESM Pro If this is do...

Page 24: ...m forwarding is not prevented If the horn has not been deactivated an alarm is always acoustically signalled at the FSZ Pro The magnet output is always switched off OFF Silent alarm OFF ON Silent alar...

Page 25: ...Class 3 Frequent use by the public and other persons with a low inclination to care and diligence i e cases where misuse is probable to a certain degree Digit 2 Stress test of the hold open device Cl...

Page 26: ...ing 9 6 1 Connection without line surveillance DIP 3 OFF The system is operated with a smoke switch stub an external manual release button and an external reset button S L HAT ORS TDS 1 3 2 BUS 6 5 4...

Page 27: ...e FACP The manual button must be simulated by a jumper ORS TDS 1 3 2 BUS 6 5 4 ORS TDS 1 3 2 BUS 6 5 4 ORS TDS 1 3 2 BUS 6 5 4 FACP O N 3 2 1 6 5 4 L N PE 24V GND ORS K B THM THM 24 V HAT RESET GND FS...

Page 28: ...switch 3 must be set to ON To prevent a short circuit remove the red and black connection wires S L HAT AM 142 ORS TDS 1 3 2 BUS 6 5 4 AM 142 O N 3 2 1 6 5 4 RD BK WH YE RD BK WH YE L N PE 24V GND ORS...

Page 29: ...n must be simulated by an AM 142 To prevent a short circuit remove the red and black connection wires L N PE 24V GND ORS K B THM THM 24 V HAT RESET GND FSZ Pro THM x AL_IN AL_IN 4 5 6 1 2 3 3 Line sur...

Page 30: ...s 2 and 3 must be set to ON To prevent a short circuit remove the red and black connection wires L N PE 24V GND ORS K B THM THM 24 V HAT RESET GND FSZ Pro THM x AL_IN AL_IN 4 5 6 1 2 3 3 Line surveill...

Page 31: ...a power failure the optical acoustic alarm device signals until the ESM Pro is discharged L N PE 24V GND ORS K B THM THM 24 V HAT RESET GND FSZ Pro THM x AL_IN AL_IN 4 5 6 1 2 3 3 Line surveillance EN...

Page 32: ...nces to indicate the different statuses Every flashing sequence starts with a long pulse 1 5 sec followed by a short pause 0 5 sec Fig 12 If flashing sequences comprise several pulses the long pulse i...

Page 33: ...l release button fault of termination module AM 142 ON OFF Flashes 3 x OFF OFF Alarm Externer alarm input Alarm of an external alarm device e g a fire alarm system ON ON OFF OFF OFF Fault at FSZ Pro F...

Page 34: ...ule and rewire HAT ON Flashes 4 x OFF OFF OFF Excess temperature in FSZ Pro Ambient temperature too high Reduce the ambient temperature install cooling if necessary ON Flashes 5 x OFF OFF OFF Fault in...

Page 35: ...also contain at least the following information Z No of the building type approval used Designation of the object of the general building type approval Name and address of the contract firm Designati...

Page 36: ...Engineering in the course of the general building type approval procedure The acceptance test must at least include the following items 1 It must be verified that the built in devices and device comb...

Page 37: ...4 FAX 07634 500 323 Abnahme durch Firmenzeichen sowie Monat und Jahr der Abnahme Feststellanlage Fig 14 A certificate of successful acceptance testing shall be issued to the operator it shall be kept...

Page 38: ...adequate instruction this functional test can be carried out by any person on their own responsibility special qualification are not required Scope results and time of the monthly respectively quarte...

Page 39: ...cular hold open system c Restoration of the fire detectors from the alarm state d Check whether there are environmental effects which affect the proper functioning of the installed hold open system e...

Page 40: ...of the hold open system according to the manufacturer s specifications e g fire detectors accumulators and or batteries d Check whether the hold open system is triggered in the event of a power failu...

Page 41: ...ination module 142 AM 142 31 5700002 01 xx Magnet line surveillance QUP 10 31 4100015 01 xx Servicing and maintenance set IW Set RS 7001949 Slide in unit FSZ QUP 10 english 31 6800001 01 xx Slide in u...

Page 42: ...2 Annex 12 3 Technical support and application support Hekatron Vertriebs GmbH Phone 49 0 76 34 5 00 8050 Br hlmatten 9 Mailto rs support hekatron de D 79295 Sulzburg V S d Werk 2 Z x x xxxx Z 6 510 2...

Page 43: ...lications 13 Functional test 39 G General safety information 5 H Hold open control unit 7 Horn 7 Horn OFF 21 I Installing the FSZ Pro 12 IW Set 40 L LED 33 Line length 15 Line surveillance 21 M Mainte...

Page 44: ...44...

Page 45: ...45 128 128 36 36 8 Bohrschablone Textanker...

Page 46: ...46...

Page 47: ...47...

Page 48: ...Hekatron Vertriebs GmbH Br hlmatten 9 D 79295 Sulzburg Techn Support 49 0 7634 500 8050 A company of rs support hekatron de Securitas Gruppe Schweiz www hekatron de...

Reviews: