28
9 Electrical installation
The table below shows the statuses that may be indicated and their meaning.
LED
green
LED
orange
LED
red
THM Relay Condition
Possible cause
Remedy
ON
OFF
OFF
ON
ON
Operation
ON
OFF
ON
OFF
OFF
Alarm
Smoke switch
Automatic release or fault
of termination module
AM 142 (if installed).
Missing magnet (termina-
tion module).
No ORS 142 in the base
with the magnet.
ON
OFF
Flashes
1 x
OFF
OFF
Alarm
Internal manual
release button
Actuation of the internal
manual release button
ON
OFF
Flashes
2 x
OFF
OFF
Alarm
External manual
release button
Actuation of the external
manual release button;
fault of termination
module AM 142
ON
ON
OFF
OFF
OFF
Fault at FSZ
Basis
Fault at FSZ Basis
Replace the device
ON
Flashes
2 x
OFF
OFF
OFF
Fault in smoke
switch stub
(ORS)
System with line surveil-
lance:
Missing termination mod-
ule AM 142 or wrong DIP
switch setting or short-
circuit of the connection
line of the ORS.
System with line
surveillance:
Connect the termina-
tion module AM 142
or set the DIP switches
according to the circuit
configuration or check
and reconnect the lines.