6 Sensors
14
Digital Governor Basic System PANDAROS II
6.2.3
Tooth profile
Any tooth profile is admissible. The top width of the tooth should be 2.5 mm minimum,
the gap and the depth of the gap at least 4 mm. For index plates the same dimensions are
valid.
Due to tolerances, a radial arrangement of the magnetic pick-up is preferable.
6.2.4
Clearance of magnetic pick-up
The distance between the magnetic pulse pick-up and the tooth top should range from
0.5 and 0.8 mm. (It is possible to screw in the magnetic pick-up till it touches the tooth
and then unscrew it for about half a turn)
Fig. 2: Clerance of pick-up