Heinrichs Messtechnik GmbH
OPERATING MANUAL TMU / UMC3
Page 23 of 122
Process pressure range
According to PN16 (Class 150) and PN40 (Class 300) etc. pressure ratings.
Outlet pressure
Outlet pressure must be greater than the vapor pressure P
s
of the measured product.
Connection to the transmitter
3.4.10.1
Integral mount configuration
When the transmitter is mounted directly on the sensor, no cable connection between the two components is
needed. This connection is assembled at the factory.
3.4.10.2
Remote mount configuration
If the transmitter is not mounted directly on the sensor, installation regulations and applicable legal standards
are to be adhered to.
The maximum cable length is 200 m (approx. 650 ft). See Section 5.1.3 on page 46 for information regarding
the connection and cable specifications.