Adopts MCU Processing 

 

Manual Test / Auto-Reset

 

Hush Function

 

Low Voltage Compensation

 

Low Battery Warning

● 

Auto-Check  Malfunction in Smoke Chamber

 

Anti-RF Interference (20V/m-1GHz)

● 

Dustproof, Mothproof, Anti-light Interference

● 

SMT Manufacture Technology with High Reliability

● 

Shockproof Design Suitable for Vehicle Use 

● 

Detects Smoke

 

INSTALLATION

1. Since the smoke density generated in fires will rise in the air,  

normally  the  detector  is  installed  in  a  higher  position.  For 

wall  mounted,  install  at    about  0.3-1.0m  from  ceiling.  For 

ceiling mounted,   normally install at the ceiling center of the 

protected area  (refer to the following image)

2. Fix the detector base into a wall or ceiling  with  screws  and 

fasten the detector head on the base.

3. While installing at home, keep the detector away from your 

gas  stove  to  prevent  flame  roasting.  Avoid  installing  in 

places with heavy oil or smoke that may cause false alarm or 

block  the  gas  convection  holes  and  influence  the  detector 

sensitivity.  Also  do  not  install  the  detector  near  to  exhaust 

fans,  windows,  doors  and  in  places  with  great  vapor  in 

bathrooms.

C

E I L I N G

F L O O R

D

E T E C T O R

G A S B U R N ER

        

User Manual of Smoke Detector

TECHNICAL PARAMETER

1

PRODUCT INTRODUCTION

PRODUCT PROFILE

FEATURES

This product is a smoke detector. The smoke chamber using the 

principle  of  smoke  particles  reflecting  infrared  lights  can 

a c c u r a t e l y  d e t e c t  t h e  e a r l y  s m o k e  o f  a  f i r e .  W h e n 

concentration  of  the  smoke  density  reaches  the  given  alarm 

level, the detector LED flashes red and buzzer gives out alarm 

sounds.  Besides 

suitable  for  early  warning  and  protection  of 

carbon monoxide leakages or fires in houses, villas, factories, 

shopping  malls,  warehouses,  office  buildings  etc.  indoor 

places, this unit has a subtle shockproof design, which makes it 

also suitable for vehicle use.

OPERATING PRINCIPLE

1. Insert 2pcs 1.5V AA batteries into the battery compartment. 

The  detector  enters  into  normal  working  status.  The  green 

LED flashes every 30S to indicate normal power supply.

2. The detector should be tested periodically during use. Short 

press Test & Hush Button to run a test. The LED flashes Red 

along with buzzer sounding for alarm indication. Do not test 

the  detector  too  often  to  save  battery  life.  Once  a  month  is 

recommended.

Operating Voltage

DC 3V (2pcs AA alkaline batteries)

Static Current

15uA

Alarm Current

35mA

Hush Time

10 minutes

Smoke Sensitivity

Alarm Indication

Failure Indication

Sound Level

Working Environment

Installation Mode

Dimension

Execute Criterion

0.2dB/m(±0.05dB/m)

Red LED

Yellow LED

85dB/3m

-10°C ~ +50°C

Wall or Ceiling mounted

Φ

110*45mm

EN14604-2005, GB15322.5-2003

1

Test 

Hush

 

Button

LED Indicator

Battery Compartment

M201-1EVer1.0

 Humidity

95RH (no condensation) 