71
Manifold not balanced
properly. One appliance
getting more than its
share of the total flow of
hot water.
Balance the system by
adjusting the flow of
water to the different
heating appliances.
Refer to
“installation Manual.”
Outdoor furnace water
temperature is not
consistently between
165 and 185 degrees
Fahrenheit.
Refer to
“installation Manual”
Over time, (approx. five
years) with some water
conditions, the sidearm
will clog up with scale
(lime) and restrict or shut
off the flow completely
through the sidearm.
Refer to
“installation Manual.”
Improper hook up of the
sidearm exchanger.
Refer to
“installation Manual.”
Water
temperature
doesn’t
correspond
with controller
settings.
Inadequate rate of flow of
water allowing layering of
water temperatures.
Flow should be at least
ten gallons per minute.
Check pump and
installation.
Refer to
“installation Manual.”
No contact paste applied
to well of Temperature
Probe and / or High Limit
Aquastat.
Remove Temperature
Probe from well and
apply paste.
Refer to
“electrical (temperature
Probe)”
Faulty Electronic
Controller.
Replace Electronic
Controller.
Refer to
“electrical (electronic
controller)”
PrOBLeM
cause
sOLutiOn
PrOceDure