39
Chart
II
Check
Central
Heating Operation
Ensure extern al
controls are calling
for h eat
Is F1 failure code
shown on lc d?
Put CH tem perature
selec tor
to maximum
NO
Does pump run?
NO
Is 23 0 V AC present on
ter m inal s of pum p and
main P CB?
YES
Check and if
nec essary repl ace
CH supply / return
sen sor
Go to Chart IV
Is F3 failure code
shown on lc d?
YES
NO
YES
Re set C ontrol
Check and if necessary
replace overheat
thermostat, check
pump
Check CH supply sensor
YES
Check and if
necessary
repl ace
Main PCB
NO
Check External CH
control input s and
wiring
Check, and if
necessary replace
main P CB
Check cab le
connections of fan, and
if n ecessary rep lace
fan
.
or repl ace main
PCB
Check cleaning of
fan, and if necessary
replace fan
Chart
III
Fan
Operation
Is 24 V dc pres ent on X4-
1-3 terminals?
NO
YES
Check, an d if necessary
repl ace m ain PCB
Go to Chart I
YES
Re set control if
neccesary
Does fan run?
Was F8 failure code
shown on lcd befor e
re set? Is F8 shown
after 1 minut
e
?
NO
NO
YES
Check fan’s cab le
connections
Check X4 connectors
for examining
switching and feedback
signals on m ain boa rd
by osiloscope.
Was F8 failure code
shown on lcd before
re set? Is F8 shown
after 1 minute?