38
NOTE:
When installing, commissioning or servicing a gas appliance that incorporates a pre-mix burner
and zero-set governor, because it is not possible to measure an operating pressure the engineer
should
fi
rst check that the gas supply is metered and ascertain whether it is possible to measure
the gas rate. If the gas input rate can be measured then the requirements of GSIUR 26(9) can be
met, including any speci
fi
c requirements in manufacturers’ instructions. If gas input rate cannot
be measured then, to satisfy the intent of GSIUR 26(9), the engineer shall measure the combustion
quality of the appliance in accordance with BS 7967 or the technical data of this manual.
If the engineer does not have the required equipment and no alternative test is speci
fi
ed
by the manufacturer then the appliance shall be turned off and disconnected as
an un-commissioned appliance until such time that equipment is available to undertake such
tests.
Chart I
Check electrical supply - C.H. Sensor and frost protection
Check the following carefully before starting
•
Gas supply is on, adequate and purged.
•
Electric supply is on.
•
Polarity is correct.
•
Pump spins freely.
Winter mode is selected by function
knob on front panel.
CH system pressure is must
be between 1 and 2 bar.
Check low water
pressure switch cable
connections.
Check and if necessary
replace low water
pressure switch.
Check suppy lead,
F1 -F2 fuse and replace
if necessary.
Replace interface
card.
Is lcd display on?
Is led display on?
Is F0 failure code shown on lcd?
Fill up system to 1 - 2 bar.
NO
NO
YES
YES
YES
YES
YES
NO
NO
YES
NO
NO
YES
YES
NO
NO
Replace main
PCB
NO
Is 230 V ac present on
terminals X15?
Is water pressure
between 1 and 2 bar?
YES
NO
NO
Does fan at full
speed?
Check pump connection cables
and 230 V ac supplying of pump.
Check CH sensor
cable connections.
Is F3 failure code
shown on lcd?
Change main PCB.
Check supply lead.
Does pump run?
Does burner work?
Go to Chart V
Go to Chart III
Is F3 failure code shown on lcd?
NO and F7 or F8 or F9 failure code showing on lcd.
Does pump run?
If temperature of the system is less then 6°C, frost protection
system is activated and snow symbol in shown on lcd display.
Select the CH position.
20. Fault Finding Chart