background image

3.

 

D.H.W. temperature control The position of this 
control dial will determine the temperature of the 
domestic hot water delivered to the taps or 
shower unit. The water temperature can be set 
from a minimum of 35º C (anticlockwise stop 
position) to a maximum of 64º C (clockwise stop 
position.) 

 
4.

 

Boiler On The boiler ‘Stand by’ indicator (green) 
lights when power is supplied to the PCB. 

 
5.

 

Water Temperature The temperature of the 
water leaving the boiler is given by the red light 
indicators situated alongside the burner 'Stand 
by' indicator light.   

 
6.

 

Fault Indicator The control unit has an in-built 
fault diagnostic function. When a fault occurs, the 
type of fault is indicated by the appropriately 
'flashing' red light indicator. A listing of the 
display lights and meanings can be found in 
Section  13  of  the  Installation and  Servicing 
Instructions. 

 
7.

 

Boiler Lockout When the first red light indicator 
from right (flame or gas fault) or the second from 
right (overheat fault) lights, the boiler will need to 
re-set.  To re-set the boiler the function switch 

must be switched to the 

 

 position and after 30 

seconds back to its previous (summer or winter) 
position. 

 
8.

 

Pressure gauge The pointer on the gauge 
indicates the pressure within the boiler and 
central heating system and should, when the 
water is cold, read between 1 and 2bar. 

 
If the pressure gauge falls below 1bar the system and 
boiler must be re-pressurised via the filling loop.  The 
filling loop should be located below the boiler.  

 

 
 

 

FROST PROTECTION 

 
The  boiler has a built  in frost  protection device that 
protects the boiler from freezing. If the boiler is to be 
left and there is a risk of frost, ensure that the gas and 
electrical supplies are left connected. The frost 
protection device  will light the boiler when the 
temperature of the boiler water falls below 6

o

C. When 

the temperature reaches 15

o

C, the boiler  will shut 

down.  
Note: This device works irrespective of any room 
thermostat setting and will  protect  the  boiler,           

but not necessarily  the  full system.  Ensure that 
vulnerable sections of the circuit are adequately lagged. 

 

SYSTEM PRESSURE 

 

On installation your installer will have filled the boiler 
and system to its effective working pressure. The 
boiler's pressure gauge should be regularly checked to 
ensure that this pressure is maintained between 1 and 
2 bar. If there is a significant or frequent drop in 
pressure then your installer should be consulted.  

 
OPERATING THE BOILER 

 

On installation your installer will have filled the boiler 
and system to its effective working pressure. The 
boiler's pressure sensor should be regularly checked 
on the LED to ensure that this pressure is maintained 
between 1 and 2 bar. If there is a significant loss in 
pressure the boiler will lock out.  The system may be 
re-charged by opening the filling  loop to charge the 
system back up to 1.5 bar as indicated on the LED panel.  
DO NOT OVERCHARGE THE BOILER PRESSURE 
BEYOND  2 BAR AS THE BOILER WILL NOT OPERATE.  
The filling loop, a flexible hose with two valves, should 
be located below the boiler connecting the second pipe 
on the right to either one of the outer pipes, see 

Figure 

10.  DO NOT CLOSE ANY OF THE FOUR VALVES 
DIRECTLY CONNECTING TO THE BOILER.  If the boiler

 

frequently loses pressure then your installer should be 
consulted.  

CLEANING 
The boiler casing may be cleaned with a damp cloth 
followed by a dry cloth to polish. Do not use abrasive or 
solvent cleaners. 

FURTHER ADVICE 

Note. A Service Engineer must be contacted if a boiler 
fault continues to occur. 

Page 37

For further information or advice (UK) contact Heatline

TM

:

Service please call:  

0870 609 2091

Spares please call: 

 

0870 777 8402

Technical assistance please call:  0870 777 8318

Or by E mail on our Web Site at www.heatline.co.uk   

37

Summary of Contents for capriz 25

Page 1: ...capriz 25 capriz 28 Installation Servicing User Instructions www heatline co uk Condensing Wall Mounted Combination Boiler...

Page 2: ...quality materials enabling reliability and optimum performance HeatlineTM is committed to the continual development of their appliances to ensure their customers benefit from the latest advances in co...

Page 3: ...e G 8 3 1 s n o i t c e n n o C l a c i r t c e l E 9 5 1 n o i t a l l a t s n I r e l i o B 0 1 6 1 y l p p u S s a G 1 1 7 1 m e t s y S e h t g n i l l i F 2 1 7 1 s n o i t c n u F l e n a P l o...

Page 4: ...rdance with these instructions and all the regulations currently in force Read these instructions carefully before installing or using the appliance Manual Handling As this appliance is heavy it is re...

Page 5: ...e Store the appliance upright as indicated on the box The Signs on B The sign of approval the Capriz 25 Capriz 28 boilers have been certified by IMQ Italy ox LOW VOLTAGE ROOM THERMOSTAT This picture s...

Page 6: ...s BS 5440 Flues and Ventilation for gas appliances of rated input not exceeding 70kW Part 1 Flues BS 5440 Flues and Ventilation for gas appliances of rated input not exceeding 70kW Part 2 Air Supply B...

Page 7: ...5 0 8 3 1 5 0 8 Domestic water supply pressure Bar PMS Min 8 0 25 8 0 25 Expansion Vessel Capacity Litres 7 Expansion Vessel Pre charge Pressure bar 1 Domestic Water Supply Output at 30 C T Lt min 11...

Page 8: ...ode 18 Heating Circuit Pressure Safety Valve 19 Secondary Heat Exchanger Plate H E 20 Automatic Air Vent 21 Water Pressure Switch Sensor 22 Pump 23 Gas Valve 24 D H W Flow Sensor 25 Filter Valve Below...

Page 9: ...maximum of 64 C 3 7 An integral pump located in the boilers main hydraulic circuit circulates water through the primary heat exchanger to either the central heating circuit or D H W heat exchanger dep...

Page 10: ...st during the installation In particular do not allow debris to enter the top of the boiler where the flue connection is made This may cause the fan outlet to get blocked or combustion chamber to fill...

Page 11: ...ged operation of the boiler is expected at temperatures below 60 C a by pass must be installed on the boiler outlet in order to prevent condensation forming inside the combustion chamber Failure to co...

Page 12: ...ive condensation occurring within the boiler flue the boiler should wherever possible be sited to ensure the shortest possible flue run is utilised 6 8 For compartment installation the requirements of...

Page 13: ...m o r F L 0 0 5 1 l l a w e m a s e h t n o l a n i m r e t a m o r f y l l a c i t r e V M 0 0 3 l l a w e m a s e h t n o l a n i m r e t a m o r f y l l a t n o z i r o H N P 0 0 6 l a n i m r e t...

Page 14: ...e less than 1 m the restrictor air diaphragm figure 6 must be fitted on the combination boiler Please find the information sheet for the installation of restrictor given with documentation group The d...

Page 15: ...rcuit board as indicated in Figure 8 Cut the existing link and connect the wires into the thermostat circuit 9 6 Ensure that the polarity of the mains connection is correct as reversed polarity may ca...

Page 16: ...AL HEATING SENSOR THREE WAY VALVE PUMP FAN PRINTED CIRCUIT BOARD L E N 230V 50Hz PERMANENT MAINS SUPPLY FUSED AT 3A 24V ROOM THERMOSTAT CONNECTION low voltage 24V TIME CLOCK low voltage 230V ROOM THER...

Page 17: ...00 B 169 C 60 100 10 4 When cutting the flue hole it is recommended that a 105mm diameter core drill is used where both internal and external access for the flue installation is available Where only i...

Page 18: ...ate trap by turning anti clockwise and fill it with approximately 50 cc water re connecting it to the boiler Figure 16 10 18 Connect the condensate drainage pipe to the drainage system Figure 16 Note...

Page 19: ...l control unit monitors and adjusts both the boiler s hydraulic circuit and D H W water outlet temperatures by means of sensors located on the Central heating and D H W flow outlets The sensors electr...

Page 20: ...bank of dip switches to allow adjustment to its pre set parameters These are situated on the rear of the control panel The potentiometers can easily be accessed by removing the cover on the rear of co...

Page 21: ...the designed central heating system requirements Figure 23 16 1 A hydraulically operated primary pressure sensor monitors water pressure or water shortage in the primary hydraulic circuit and will swi...

Page 22: ...s LED ON Create demand Bar LED Flashing Is 240 Vac present at pin X15 on PCB Fan running at full speed LED ON Does pump run now Check low water pressure switch cables connections clean or replace as r...

Page 23: ...ut Check burner injectors gas pressures probe Check gas valve gas supply and pressu res Check ignition and ionisation probes for correct position damage Go to Chart 5 Go to Chart 5 Replace PCB Check r...

Page 24: ...ir retaining hooks Figure 26 Release the side panels by removing the screws on the upper and lower sides Figure 27 Remove the panels by swinging them out and lifting them up 18 6 Remove the combustion...

Page 25: ...key into the outlet and remove the sump by turning anti clockwise Clean the sump using a dilute solution of bleach Apply a little silicone grease to the O ring and replace the sump so that the O ring...

Page 26: ...it seals before re filling the boiler 19 3 For replacement of the following components it will be necessary to remove the boiler casing panels as described in Section 17 19 4 Domestic hot water sensor...

Page 27: ...ctors and tighten ensuring that the injector size marked on each injector is the same as stated in the Technical Data section for the type of gas being used Replace the burner bar and re fit the burne...

Page 28: ...the pump body Remove the motor as described above Remove the secondary water to water heat exchanger as detailed in 19 12 Remove the expansion vessel pipe by removing the clip on the pump body Remove...

Page 29: ...ensuring all washers are fitted Replace damaged washers as necessary Open the isolating valves on the flow and return connections refill vent and re pressurise the system ensuring all joints are sound...

Page 30: ...ler is turned off Disconnect the electrical connections to gas valve modulating coil Release the connection from gas valve and manifold inlet retaining the washers for use on reassembly Figure 47 Rele...

Page 31: ...kwise to increase Anti clockwise to decrease Re connect the lead of gas valve coil After adjustment refit plastic cap on gas valve adjuster and remove gauge and leak test pressure test point 19 16 Exp...

Page 32: ...ring all joints are sound 19 19 Hydroblock Drain the boiler s hydraulic circuit as detailed in 19 2 Remove the secondary heat exchanger as described in 19 12 Remove the pump assembly as described in 1...

Page 33: ...connection from the boiler Either pop out the filter with a screw driver or disconnect the filter housing from the bottom of the hydroblock using a 24mm spanner Pop out the filter and clean or replace...

Page 34: ...the gas circuit for soundness and the correct operation of the boiler 20 Gas Type Conversion Warning Gas conversion must be carried out by a competent person as defined in the Gas Safety and Use Regu...

Page 35: ...003202166 12 SECONDARY HEAT EXCHANGER 24 kW SECONDARY HEAT EXCHANGER 30 kW 3003200026 3003200025 3003200183 3003200176 3003200177 3003202174 D R A C E C A F R E T N I 3 1 2 5 1 0 0 2 3 0 0 3 R O S N E...

Page 36: ...www heatline co uk 25 28 Condensing Wall Mounted Combination Boiler User Instructions 34...

Page 37: ...nce should not be used until fault has been rectified by a competent person VENTILATION On installation the boiler must be installed with minimum clearances of 50mm each side 200mm above 300mm below w...

Page 38: ...run after shut down for a short while to dissipate any excess heat within the boiler ACCESS TO THE BOILER CONTROLS The boiler controls are sited at the bottom of the boiler s front case figure 1 BOIL...

Page 39: ...ure of the boiler water falls below 6 o C When the temperature reaches 15 o C the boiler will shut down Note This device works irrespective of any room thermostat setting and will protect the boiler b...

Page 40: ...Page 38 3005114697 38...

Page 41: ...3003202303 01 Page 39 39...

Page 42: ...Heatline Nottingham Road Belper Derbyshire DE56 1JT Tel 01773 596 099 Fax 01773 828 123 Email sales heatline co uk www heatline co uk...

Reviews: