Beacon II Controller
Programming And Reviewing Settings/Changes (continued)
Use this button to
“CLEAR/TEST”
Pressing this button ONCE will return the LED display to the default display.
With the system in the
OFF
mode, pressing and holding this button will start the
“TEST”
mode. In the
“TEST”
mode it will cycle through each output.
STATUS INDICATOR LED
A red, 3-digit, alphanumeric LED on the Beacon II board indicates status, alarms
and error codes.
Status
LED Display
Description
• OFF
Box Temp /
oFF
Box Temperature / Mode is displayed
All Evaporators
•COOLING
Single Evaporator –
Box Temp /
Coo
Box Temperature / Mode is displayed
Multiple Evaporators
Master Evap –
Box Temp /
Coo
Box Temperature / Mode is displayed
Slave Evaps –
Coo
Operating Mode is displayed
• Pumpdown
All Evaporators
Pdn
• DEFROST
All Evaporators
dEF
• TEST
All Evaporators
tSt
•SERVICE
All Evaporators
SEr
• ALARMS
A1
High Box Temp
A2
Low Box Temp
A3
System Start-Up Failure
Compressor does not start after 3 times.
(Four minutes between each try)
A4
Input Fault
Box Temp., Suction Temp., Pressure
Transducer open or not installed
CLEAR /
TEST