Heatcraft Refrigeration Products Condensing Units H-IM-CU Installating And Operation Manual Download Page 6

CAUTION: 

Under no circumstance should all condenser motors be allowed to cycle off on one control. At least one motor shall be wired to operate at all times. 

Under most circumstances, the condenser motor nearest the inlet header should remain on whenever the compressor is operating.

CAUTION: 

Fans closest to the headers should not be cycled on standard temperature or pressure controls. Dramatic temperature and pressure changes at the 

headers as a result of fan action can result in possible tube failure. Fan motors are designed for continuous duty operation.  

Fan cycling controls should be adjusted to maintain a minimum of (5) minutes on and (5) minutes off. Short cycling of fans may result in a 

premature failure of motor and/or fan blade. 

Compressors operating below +10°F SST must have air flowing over the compressor at all times when the compressor is running.

Figure .  Dual Valve Piping Arrangement

Figure 7.  Single Valve Flooding Valve Piping Arrangement

Head Pressure Control

Several types of head pressure control systems are available on  

condensing units:

Dual Valve System. (See section on operation and adjustment.)
Single Valve system. No adjustments are necessary.    

 

 

(See section on operation.)
Ambient Fan Cycle Control. (See section on operation  

 

and adjustment.)

A.  Dual Valve System

The system employs an ORI (open on rise of inlet pressure) valve and an ORD 

( open on rise of differential pressure) valve. The high pressure discharge gas  

is introduced above the liquid in the receiver tank. The receiver discharge is 

regulated by the ORI valve.
The discharge pressure of the ORI valve must be adjusted to regulate the unit 

for proper operating conditions. Adjust the ORI valve shown on the following 

diagram to maintain a discharge pressure of 160 to 180 PSIG.

A.
B.

C.

Table 1.  Ambient Fan Cycle Thermostat Settings

Models

Design

Thermostat Settings

T.D.

T1

T2

T

30

60

2-fan units:

25

65

20

70

4-fan units:

15

75

30

60

40

3-fan units:

25

65

55

20

70

60

6-fan units:

15

75

65

30

60

50

30

8-fan units:

25

65

55

40

20

70

65

50

15

75

70

60

NOTE:   Cycle pairs of fans on double wide units.

Operation and Adjustment

Condensing units with dual valves require sufficient charge to partially flood 

the condenser during low ambient conditions.
Valve adjustment should be made with gauges connected to the discharge 

port of the compressor. Adjustments should be made during mild or 

low ambient conditions. Turning the valve stem “clockwise” on the ORI 

valve will increase the discharge pressure, while turning the valve stem 

“counterclockwise” will decrease the discharge pressure.
If adjustments are made during warm ambient conditions, it may not be 

possible to adjust the regulator valve as low as desired.  Readjustment may 

be necessary once cooler conditions prevail.

B.  Single Valve System 

The standard valve used on high pressure refrigerant systems controls 

the head pressure at approximately 180 PSIG. There is no adjustment for 

this valve. On low pressure refrigerant systems the valve controls pressure 

at approximately 100 PSIG.  For energy efficiency, the 100 PSIG valve is 

sometimes used on high pressure refrigerant systems.
At condensing pressures above the valve setting, flow enters Port C and 

leaves Port R. When the condensing pressure falls below the valve setting, 

the valve modulates to permit discharge gas to enter Port D. Metering 

discharge gas into the refrigerant flow leaving the condenser produces a 

higher pressure at the condenser outlet, reduces the flow, and causes the 

level of liquid refrigerant to rise in the condenser. This “flooding” of the 

condenser with liquid refrigerant reduces the available condensing surface, 

holding the condensing pressure at the valve setting.

C.  Ambient Fan Cycle Control

This is an automatic winter control method which will maintain a condensing 

pressure within reasonable limits by cycling fan motors in response to 

outside air temperature. The thermostat(s) should be field adjusted to shut 

off the fan when the condensing temperature is reduced to approximately 

90

˚

F. Table 1 lists approximate settings for several system T.D.’s. These settings 

are approximate as they do not take into account variations in load.

Summary of Contents for Condensing Units H-IM-CU

Page 1: ...or 8 Recommended Refrigerant Piping Practices 8 Refrigeration Pipe Supports 8 Suction Lines 8 Liquid Lines 9 Hot Gas Defrost Systems 9 Unit Cooler Piping 10 Line Sizing Tables 10 13 Evacuation and Lea...

Page 2: ...s factory and no freight shall be allowed for transportation of the motor compressor to and from the wholesaler The replacement motor compressor shall be identical to the model of the motor compresso...

Page 3: ...top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free area with 1 foot undercut a W minimum clearance and must not exceed the top of unit If these requirements are n...

Page 4: ...where incoming water is 75 F and condensing temperature is 105 F Tower refers to a higher temperature relationship which is normally 85 F incoming water and 105 F condensing temperature Water circuit...

Page 5: ...units a structural analysis by a qualified engineer may be required before mounting Roof mounted units should be installed level on steel channels or an I beam frame capable of supporting the weight o...

Page 6: ...50 30 8 fan units 25 65 55 40 20 70 65 50 15 75 70 60 NOTE Cycle pairs of fans on double wide units Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 7: ...which oils lubricants are approved for use in Copeland compressors Mineral Oils The BR and Scroll compressors use Sontex 200 a white oil This oil is not suitable for low temperature applications nor i...

Page 8: ...at the base of each suction riser to enhance oil return to the compressor For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximi...

Page 9: ...freezing The hot gas exits the loop at the pan loop outlet header and enters the evaporator through the check valve assembly As the hot gas defrosts the coil heat is removed from the hot gas and even...

Page 10: ...rator Refer to Table 5 Each 1 1 8 90 elbow adds 3 equivalent feet of pipe Each 90 turn through a 1 1 8 tee adds 6 equivalent feet Actual line run evap 1 105 feet 5 1 1 8 elbows 3 15 feet 1 90 turn thr...

Page 11: ...0 3 8 3 8 3 8 3 8 6 000 50 3 8 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 9 000 50 1 2 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 12 000 50 1 2 3 8 1 2 3 8 100 5 8 3 8 5 8 1 2 18 000 50 5 8 3 8 5 8 1 2 100 5 8 3 8 7 8 1 2...

Page 12: ...1 5 8 1 3 8 1 5 8 1 5 8 2 1 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 3 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 5 8 2 1 8 2 1 8 1 2...

Page 13: ...5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 3 8 1 5 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8...

Page 14: ...lve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is reached at which time the vacuum should be broken with the refrigerant to be used in the system through a...

Page 15: ...re has stabilized Observe system pressures during charging and initial operation Do not add oil while the system is short of refrigerant unless oil level is dangerously low Continue charging until sys...

Page 16: ...rve oil level in compressor crankcase sight glass Add oil as necessary to bring level to bottom 1 4 of the sight glass Thermostatic expansion valves must be checked for proper superheat settings Feele...

Page 17: ...ly The defrost heaters are off The room thermostat closes when the temperature rises above the desired setting The liquid line solenoid is energized and opens which allows liquid refrigerant to flow t...

Page 18: ...ol operation 2 Open valve 3 Check for leaks Repair and add charge 4 See corrective steps for low suction pressure 5 Check valve setting High suction pressure 1 Excessive load 2 Expansion valve overfee...

Page 19: ...Check unit cooler superheat and compare reading for your specific application Visually inspect coil for even distribution Check moisture indicator sightglass for flash gas If found check entire syste...

Page 20: ...20 Diagram 3 Typical Wiring Diagram for Single Evaporator with and without Defrost Timer Diagram 4 Typical Wiring Diagram for Single Evaporator with Defrost Timer Only...

Page 21: ...21 Diagram 5 Typical Wiring Diagram for Multiple Evaporators with Defrost Timer Only Diagram 6 Typical Wiring Diagram for Single Evaporator Single Phase Defrost and Evaporator Fan Contactors...

Page 22: ...ram 7 Typical Wiring Diagram for Single Evaporator Defrost and Evaporator Fan Contactors Diagram 8 Typical Wiring Diagram for Multiple Evaporators with Evaporator Fan Contactors without Heater Limit D...

Page 23: ...Wiring Diagram for Multiple Evaporators Defrost and Evaporator Fan Contactors with Unit Cooler Holdout Relay Diagram 9 Typical Wiring Diagram for Multiple Evaporators with Heater Limit Defrost and Eva...

Page 24: ...the same high performance standards with which all HRP brands are built backed by a dedicated team to serve every customer need delivering at the best lead times in the industry Replacement parts sho...

Reviews: