Heatcraft Refrigeration Products Condensing Units H-IM-CU Installating And Operation Manual Download Page 3

© 2008 Heatcraft Refrigeration Products LLC

The most important consideration which must be taken into account when 

deciding upon the location of air-cooled equipment is the provision for a 

supply of ambient air to the condenser, and removal of heated air from the 

condensing unit or remote condenser area.  Where this essential requirement 

is not adhered to, it will result in higher head pressures, which cause poor 

operation and potential failure of equipment. Units must not be located 

in the vicinity of steam, hot air or fume exhausts. Corrosive atmospheres 

require custom designed condensers.

Another consideration which must be taken is that the unit should be 

mounted away from noise sensitive spaces and must have adequate support 

to avoid vibration and noise transmission into the building. Units should be 

mounted over corridors, utility areas, rest rooms and other auxiliary areas 

where high levels of sound are not an important factor. Sound and structural 

consultants should be retained for recommendations.

Space and Location Requirements for 
Air Cooled Condensing Units and Remote Condensers

Figure 1. Space and Location Requirements for Condensing Units

Units in Pits

The top of the unit should be level with the top of the pit, and side 

distance increased to “2W”.
If the top of the unit is not level with the top of pit, discharge cones or 

stacks must be used to raise discharge air to the top of the pit. This is a 

minimum requirement.

Decorative Fences

Fences must have 50% free area, with 1 foot undercut, a “W” 

minimum clearance, and must not exceed the top of unit. If these 

requirements are not met, unit must be installed as indicated for 

“Units in pits”.

Walls or Obstructions

The unit should be located so that air may circulate freely and not be 

recirculated. For proper air flow and access all sides of the unit should be 

a minimum of “W” away from any wall or obstruction. It is preferred that 

this distance be increased whenever possible. Care should be taken to 

see that ample room is left for maintenance work through access doors 

and panels. Overhead obstructions are not permitted. When the unit is 

in an area where it is enclosed by three walls the unit must be installed 

as indicated for units in a pit.

Walls or Obstructions for Horizontal Air Flow

Multiple Units with Horizontal Air Flow

* “W” = Total width of the condensing unit

Multiple Units

For units placed side by side, the minimum distance between 

units is the width of the largest unit. If units are placed end to 

end, the minimum distance between units is 4 feet.

W

MIN.

W

AIR FL

O

W

W

AIR FL

O

W

W

W

W

MIN.

W

AIR FLOW

AIR FLOW

W

Clearance for multiple units placed side by side

AIR FLOW

AIR FLOW

AIR FLOW

W

W

MIN.

W

MIN.

1 FT. MIN.

Clearance for fence enclosures

AIR FLOW

2W

MIN.

2W

MIN.

10 FT. MAX.

W

Clearance for units in pits

AIR FLOW

STACK

(SUPPLIED BY OTHERS)

W

W

MIN.

AIR FLOW

Clearance from walls or obstructions

AIR FLOW

NOT RECOMMENDED

AIR FLOW

W

W

AIR FLOW

W

AIR FLOW

AIR FLOW

W

W

AIR FLOW

Summary of Contents for Condensing Units H-IM-CU

Page 1: ...or 8 Recommended Refrigerant Piping Practices 8 Refrigeration Pipe Supports 8 Suction Lines 8 Liquid Lines 9 Hot Gas Defrost Systems 9 Unit Cooler Piping 10 Line Sizing Tables 10 13 Evacuation and Lea...

Page 2: ...s factory and no freight shall be allowed for transportation of the motor compressor to and from the wholesaler The replacement motor compressor shall be identical to the model of the motor compresso...

Page 3: ...top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free area with 1 foot undercut a W minimum clearance and must not exceed the top of unit If these requirements are n...

Page 4: ...where incoming water is 75 F and condensing temperature is 105 F Tower refers to a higher temperature relationship which is normally 85 F incoming water and 105 F condensing temperature Water circuit...

Page 5: ...units a structural analysis by a qualified engineer may be required before mounting Roof mounted units should be installed level on steel channels or an I beam frame capable of supporting the weight o...

Page 6: ...50 30 8 fan units 25 65 55 40 20 70 65 50 15 75 70 60 NOTE Cycle pairs of fans on double wide units Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 7: ...which oils lubricants are approved for use in Copeland compressors Mineral Oils The BR and Scroll compressors use Sontex 200 a white oil This oil is not suitable for low temperature applications nor i...

Page 8: ...at the base of each suction riser to enhance oil return to the compressor For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximi...

Page 9: ...freezing The hot gas exits the loop at the pan loop outlet header and enters the evaporator through the check valve assembly As the hot gas defrosts the coil heat is removed from the hot gas and even...

Page 10: ...rator Refer to Table 5 Each 1 1 8 90 elbow adds 3 equivalent feet of pipe Each 90 turn through a 1 1 8 tee adds 6 equivalent feet Actual line run evap 1 105 feet 5 1 1 8 elbows 3 15 feet 1 90 turn thr...

Page 11: ...0 3 8 3 8 3 8 3 8 6 000 50 3 8 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 9 000 50 1 2 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 12 000 50 1 2 3 8 1 2 3 8 100 5 8 3 8 5 8 1 2 18 000 50 5 8 3 8 5 8 1 2 100 5 8 3 8 7 8 1 2...

Page 12: ...1 5 8 1 3 8 1 5 8 1 5 8 2 1 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 3 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 5 8 2 1 8 2 1 8 1 2...

Page 13: ...5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 3 8 1 5 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8...

Page 14: ...lve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is reached at which time the vacuum should be broken with the refrigerant to be used in the system through a...

Page 15: ...re has stabilized Observe system pressures during charging and initial operation Do not add oil while the system is short of refrigerant unless oil level is dangerously low Continue charging until sys...

Page 16: ...rve oil level in compressor crankcase sight glass Add oil as necessary to bring level to bottom 1 4 of the sight glass Thermostatic expansion valves must be checked for proper superheat settings Feele...

Page 17: ...ly The defrost heaters are off The room thermostat closes when the temperature rises above the desired setting The liquid line solenoid is energized and opens which allows liquid refrigerant to flow t...

Page 18: ...ol operation 2 Open valve 3 Check for leaks Repair and add charge 4 See corrective steps for low suction pressure 5 Check valve setting High suction pressure 1 Excessive load 2 Expansion valve overfee...

Page 19: ...Check unit cooler superheat and compare reading for your specific application Visually inspect coil for even distribution Check moisture indicator sightglass for flash gas If found check entire syste...

Page 20: ...20 Diagram 3 Typical Wiring Diagram for Single Evaporator with and without Defrost Timer Diagram 4 Typical Wiring Diagram for Single Evaporator with Defrost Timer Only...

Page 21: ...21 Diagram 5 Typical Wiring Diagram for Multiple Evaporators with Defrost Timer Only Diagram 6 Typical Wiring Diagram for Single Evaporator Single Phase Defrost and Evaporator Fan Contactors...

Page 22: ...ram 7 Typical Wiring Diagram for Single Evaporator Defrost and Evaporator Fan Contactors Diagram 8 Typical Wiring Diagram for Multiple Evaporators with Evaporator Fan Contactors without Heater Limit D...

Page 23: ...Wiring Diagram for Multiple Evaporators Defrost and Evaporator Fan Contactors with Unit Cooler Holdout Relay Diagram 9 Typical Wiring Diagram for Multiple Evaporators with Heater Limit Defrost and Eva...

Page 24: ...the same high performance standards with which all HRP brands are built backed by a dedicated team to serve every customer need delivering at the best lead times in the industry Replacement parts sho...

Reviews: