Heatcraft Refrigeration Products Condensing Units H-IM-CU Installating And Operation Manual Download Page 16

1

System Balancing - Compressor Superheat

IMPORTANT:  

In order to obtain the maximum capacity from a system, and to ensure 

trouble-free operation, it is necessary to balance each and every system.

This is extremely important with any refrigeration system.
The critical value which must be checked is suction superheat.
Suction superheat should be checked 

at the compressor

 as follows:

Measure the suction pressure at the suction service valve of the  

 

 

compressor  and  determine  the  saturation  temperature  corresponding  

 

to this pressure from a  “Temperature-Pressure” chart.
Measure the suction temperature of the suction line about one  

 

 

foot back from the compressor using an accurate thermometer.
Subtract the saturated temperature from the actual  

 

 

 

suction line temperature. The difference is superheat.

Too low a suction superheat can result in liquid being returned to the 

compressor. This will cause dilution of the oil and eventual failure of the 

bearings and rings or in the extreme case, valve failure.
Too high a suction superheat will result in excessive discharge temperatures 

which cause a break down of the oil and results in piston ring wear, piston 

and cylinder wall damage.  
It should also be remembered that the system capacity decreases as the 

suction superheat increases.  For maximum system capacity, suction 

superheat should be kept as low as is practical. Copeland mandates a 

minimum

 superheat of 20˚F 

at the compressor

.  We recommend that the 

superheat 

at the compressor

 be between 20˚F and 30˚F.

If adjustments to the suction superheat need to be made, the expansion 

valve at the evaporator should be adjusted.

1.

2.

3.

Operational Check Out

After the system has been charged and has operated for at least two hours at 

normal operating conditions without any indication of malfunction, it should 

be allowed to operate overnight on automatic controls.  Then a thorough 

recheck of the entire system operation should be made as follows:

Check compressor discharge and suction pressures.    

 

 

If not within system design limits, determine why and   

 

 

take corrective action.
Check liquid line sight glass and expansion valve operation. If    

 

there are indications that more refrigerant is required, leak test    

 

all connections and system components and repair any  

 

 

leaks before adding refrigerant.  
Observe oil level in compressor crankcase sight glass.  Add oil as   

 

necessary to bring level to bottom 1/4 of the sight glass.  
Thermostatic expansion valves must be checked  

 

 

 

for proper superheat settings. Feeler bulbs must be    

 

 

in positive contact with the suction line and should    

 

 

be insulated. Valves set at high superheat will lower    

 

 

refrigeration capacity.  Low superheat promotes  

 

 

 

liquid slugging and compressor bearing washout.
Using suitable instruments, carefully check line voltage and  

 

 

amperage at the compressor terminals. Voltage must be within    

 

10% of that indicated on the condensing unit nameplate.  If high  

 

or low voltage is indicated, notify the power company.   

 

 

If amperage draw is excessive, immediately determine the cause   

 

and take corrective action.  On three phase motor compressors,    

 

check to see that a balanced load is drawn  

 

by each phase.  
The maximum approved settings for high pressure controls on    

 

our air cooled condensing equipment is 425 psig.  On air cooled    

 

systems, check as follows:   

 

Disconnect the fan motors or block the condenser inlet air.  Watch  

 

high pressure gauge for cutout point.  Recheck all safety and  

 

 

operating controls for proper operation and adjust if necessary.  
Check defrost controls for initiation and termination settings, and  

 

length of defrost period.  Set fail safe at length of d 25%. 

 

Example:   

20 minute defrost  + 5 minutes 

 

 

 

=   25 minute fail safe  

Check drain pan for proper drainage.
Check winter head pressure controls for pressure setting.
Check crankcase heater operation if used.
Install instruction card and control system diagram for  

 

 

use of building manager or owner.

a)

b)

c)

d)

e)

f)

g)

h)
i)
j)
k)

NOTE:           

All adjustable controls and valves must be field adjusted to meet desired 

operation. There are no factory preset controls or valve adjustments. This 

includes low pressure, high pressure, adjustable head pressure systems 

and expansion valves.

Table 9.  Recommended Low Pressure Control Settings for Outdoor Air Cooled Condensing Units

*Minimum 

Temp. ˚F

R-22

R-0A/R-507

Cut-In PSI

Cut-Out PSI

Cut-In PSI

Cut-Out PSI

50

70

20

90

35

40

55

20

70

35

30

40

20

55

35

10

30

10

45

25

0

15

0

25

7

-10

15

0

20

1

-20

10

0

12

1

-30

6

0

8

1"Hg.

* Minimum ambient or box temperature anticipated, high pressure control setting: R-22, 360 PSI; R-404A, R-507, 400 PSI

* The standard preset low pressure switch used for pumpdown is set for 15 PSI cut in / 4 PSI cut out and is a good setting for most pumpdown systems

* ZB Scroll compressors should be set for 25 PSI cut in / 17 PSI cut out (R-404A / R-507)

Summary of Contents for Condensing Units H-IM-CU

Page 1: ...or 8 Recommended Refrigerant Piping Practices 8 Refrigeration Pipe Supports 8 Suction Lines 8 Liquid Lines 9 Hot Gas Defrost Systems 9 Unit Cooler Piping 10 Line Sizing Tables 10 13 Evacuation and Lea...

Page 2: ...s factory and no freight shall be allowed for transportation of the motor compressor to and from the wholesaler The replacement motor compressor shall be identical to the model of the motor compresso...

Page 3: ...top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free area with 1 foot undercut a W minimum clearance and must not exceed the top of unit If these requirements are n...

Page 4: ...where incoming water is 75 F and condensing temperature is 105 F Tower refers to a higher temperature relationship which is normally 85 F incoming water and 105 F condensing temperature Water circuit...

Page 5: ...units a structural analysis by a qualified engineer may be required before mounting Roof mounted units should be installed level on steel channels or an I beam frame capable of supporting the weight o...

Page 6: ...50 30 8 fan units 25 65 55 40 20 70 65 50 15 75 70 60 NOTE Cycle pairs of fans on double wide units Operation and Adjustment Condensing units with dual valves require sufficient charge to partially f...

Page 7: ...which oils lubricants are approved for use in Copeland compressors Mineral Oils The BR and Scroll compressors use Sontex 200 a white oil This oil is not suitable for low temperature applications nor i...

Page 8: ...at the base of each suction riser to enhance oil return to the compressor For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximi...

Page 9: ...freezing The hot gas exits the loop at the pan loop outlet header and enters the evaporator through the check valve assembly As the hot gas defrosts the coil heat is removed from the hot gas and even...

Page 10: ...rator Refer to Table 5 Each 1 1 8 90 elbow adds 3 equivalent feet of pipe Each 90 turn through a 1 1 8 tee adds 6 equivalent feet Actual line run evap 1 105 feet 5 1 1 8 elbows 3 15 feet 1 90 turn thr...

Page 11: ...0 3 8 3 8 3 8 3 8 6 000 50 3 8 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 9 000 50 1 2 3 8 1 2 3 8 100 1 2 3 8 1 2 3 8 12 000 50 1 2 3 8 1 2 3 8 100 5 8 3 8 5 8 1 2 18 000 50 5 8 3 8 5 8 1 2 100 5 8 3 8 7 8 1 2...

Page 12: ...1 5 8 1 3 8 1 5 8 1 5 8 2 1 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 1 8 1 3 8 1 3 8 1 1 8 1 3 8 1 3 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 3 8 1 5 8 2 1 8 1 3 8 1 5 8 2 1 8 2 1 8 1 2...

Page 13: ...5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 2 1 2 5 8 5 8 72 000 1 1 8 1 3 8 1 5 8 1 5 8 1 1 8 1 3 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8...

Page 14: ...lve The vacuum pump should be operated until a pressure of 1 500 microns absolute pressure is reached at which time the vacuum should be broken with the refrigerant to be used in the system through a...

Page 15: ...re has stabilized Observe system pressures during charging and initial operation Do not add oil while the system is short of refrigerant unless oil level is dangerously low Continue charging until sys...

Page 16: ...rve oil level in compressor crankcase sight glass Add oil as necessary to bring level to bottom 1 4 of the sight glass Thermostatic expansion valves must be checked for proper superheat settings Feele...

Page 17: ...ly The defrost heaters are off The room thermostat closes when the temperature rises above the desired setting The liquid line solenoid is energized and opens which allows liquid refrigerant to flow t...

Page 18: ...ol operation 2 Open valve 3 Check for leaks Repair and add charge 4 See corrective steps for low suction pressure 5 Check valve setting High suction pressure 1 Excessive load 2 Expansion valve overfee...

Page 19: ...Check unit cooler superheat and compare reading for your specific application Visually inspect coil for even distribution Check moisture indicator sightglass for flash gas If found check entire syste...

Page 20: ...20 Diagram 3 Typical Wiring Diagram for Single Evaporator with and without Defrost Timer Diagram 4 Typical Wiring Diagram for Single Evaporator with Defrost Timer Only...

Page 21: ...21 Diagram 5 Typical Wiring Diagram for Multiple Evaporators with Defrost Timer Only Diagram 6 Typical Wiring Diagram for Single Evaporator Single Phase Defrost and Evaporator Fan Contactors...

Page 22: ...ram 7 Typical Wiring Diagram for Single Evaporator Defrost and Evaporator Fan Contactors Diagram 8 Typical Wiring Diagram for Multiple Evaporators with Evaporator Fan Contactors without Heater Limit D...

Page 23: ...Wiring Diagram for Multiple Evaporators Defrost and Evaporator Fan Contactors with Unit Cooler Holdout Relay Diagram 9 Typical Wiring Diagram for Multiple Evaporators with Heater Limit Defrost and Eva...

Page 24: ...the same high performance standards with which all HRP brands are built backed by a dedicated team to serve every customer need delivering at the best lead times in the industry Replacement parts sho...

Reviews: