Heatcraft Refrigeration Products BEACON II SMART CONTROLLER H-IM-80C Installation And Operation Manual Download Page 9

9

SUPRHT

 – Superheat: 4 to 20 

°

 F. Use “SETPOINT” slide-bar to select desired

superheat temp., then press “ENTER.” If multiple evaporators are connected, use the “+”
button to set other evaporators on this system.

SMT DFT

 : Smart Defrost: On/Off. Use “SETPOINT” slide-bar to turn it ON or OFF,

then press “ENTER” - (for version 1.2. When Smart Defrost is turned on, 8 defrost periods
per day will automatically be programmed. These will be at 12:00 am, 3:00 am, 6:00 am,
9:00 am, 12:00 pm, 3:00 pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be
set to 60 minutes, and the defrost termination temperature will be set to 55

°

F. The user

can change these as needed for the application).

DEF ST

 - Defrost Start time: Up to 12 settings per day (For dF 1, use the “TIME” slide-

bar to select first defrost time, then press “ENTER”. Use + button to scroll to next defrost
period, dF 2, use “TIME” slide-bar to select second defrost time and press “ENTER”.
Repeat steps for each required defrost period).  If defrost times are not
programmed the system will use the defaults
: Electric Defrost - four per day at
4:00 AM, 10:00 PM, 4:00 PM, 10:00 AM. Air Defrost - two per day at 9:00 AM, 9:00 PM.

DEFSAF

 –  Defrost Fail Safe Time: 10 to 200 minutes.  When this time has

elapsed, the defrost cycle will end, even if the programmed Defrost Termination
temperature was not achieved. Use “SETPOINT” slide-bar to select desired time,

then press “ENTER”.

DEFTMP

 – Defrost Termination Temperature: 40 to 100

°

 F.  Use “SETPOINT”

slide-bar to select desired temp., then press “ENTER”. If multiple evaporators are
connected, use the “+” button to set other evaporators on this system.

ALR HI

 – Alarm High Temperature. -40 to 90

°

 F. Use “SETPOINT” slide-bar to

select desired temp., then press “ENTER”.

ALR LO

 – Alarm Low Temperature -40 to 90

°

 F. Use “SETPOINT” slide-bar to

select desired temp., then press “ENTER”.

ALRMIN

 – Alarm Time, in minutes. Condition must exceed before alarm is

indicated: 2 to 120 min. Use “SETPOINT” slide-bar to select desired time, then press
“ENTER”.

°

 F  / 

°

 C

  –  

°

 F or 

°

 C. Use “SETPOINT” slide-bar to select then press “ENTER”.

12/24H

 – Clock: 12H is for standard time. 24H is for international time. Use

“SETPOINT” slide-bar to select, then press “ENTER”.

TEST

 : OFF or ON: Puts all evaporators in TEST mode. Use with Caution. This will

cycle each output at 10 second intervals. Use “SETPOINT” slide-bar to select, then
press “ENTER”.  Return to “OFF” and then press “ENTER” to end the test.

SERVIC

 – ON or OFF: When placed in the ON mode this will pump the system

down and shut it off.  The system will not restart until 

SERVIC

 is placed back in the

OFF mode.

When multiple evaporators are connected as master/slave, depressing the + or -
button will display information specific to each evaporator. Units in a master/slave
connection are numbered 1 through 4. The first evaporator connected to the
BEACON II SMART CONTROLLER 

MULTI-OUT Terminals is Evaporator # 1.

MONITORING with BEACON II SMART CONTROLLER

The Monitoring function can be used to monitor live system data. The information
displayed, such as superheat, is the actual superheat of the system as it is changing.

Press the MONITOR button and follow the steps below (to back up one step during

monitoring, while pressing the “PROG REVIEW” button, press the “MONITOR” button):

SUPRHT

 – Superheat (use + button to check superheat of other evaporators, if

Master/slave)

Monitoring With Beacon II Smart Controller

Summary of Contents for BEACON II SMART CONTROLLER H-IM-80C

Page 1: ...Beacon II Smart Controller 7 Button Functions 7 Programming Beacon II Smart Controller 8 Monitoring Beacon II Smart Controller 9 Locking Beacon II Smart Controller 10 Error Codes 10 Wiring Errors 11...

Page 2: ...Controller allows complete monitoring and programming of the system The Controller display has the following buttons COOLING DEFROST PROG REVIEW MONITOR ENTER CLEAR SETPOINT AND TIME The normal LCD d...

Page 3: ...Alarm condition Can be mounted up to 1000 ft away from the system being controlled Each Beacon II Smart Controller can control four independent systems with up to 4 evaporators on each system An RS23...

Page 4: ...rt Controller should not be mounted where it will experience temperatures below 40 F or above 100 F A terminal strip for wiring connections is located on the base of the Beacon II Smart Controller To...

Page 5: ...o the MULTI OUT on the Beacon board on the Evaporator See typical wiring diagram at the back of these instructions On systems with multiple evaporators the Beacon II Smart Controller must be wired to...

Page 6: ...18 gauge wire should be used All low voltage wiring must be run separate from high voltage wiring MULTIPLE SYSTEM CONNECTION SYSTEM 1 SYSTEM 2 SYSTEM 3 SYSTEM 4 M Master Evaporator S Slave Evaporator...

Page 7: ...he Beacon II Smart Controller Make sure all wiring changes to the system and the Beacon II Smart Controller are complete and accurate before initializing the Beacon II Smart Controller Each SLAVE Evap...

Page 8: ...changes If multiple evaporators are connected to the system displayed you must press the or buttons to display information on the evaporator you want to monitor CLEAR Used to clear incorrect entries w...

Page 9: ...ther evaporators on this system ALR HI Alarm High Temperature 40 to 90 F Use SETPOINT slide bar to select desired temp then press ENTER ALR LO Alarm Low Temperature 40 to 90 F Use SETPOINT slide bar t...

Page 10: ...sing the or button will display information specific to each evaporator Units in a master slave connection are numbered 1 through 4 The first evaporator connected to the BEACON II SMART CONTROLLER MUL...

Page 11: ...ion wiring is the MULTI IN and MULTI OUT connections Check to make sure the OUT is connected to IN Never connect OUT to OUT or IN to IN ALARM CODES BOXHI Box temperature too high BOXLO Box temperature...

Page 12: ...length of time it records data is dependent on how many systems are being controlled by the Beacon II Smart Controller It keeps writing data to its memory until the memory is full When the memory is f...

Page 13: ...m to defrost the coil properly Smart Defrost will only allow the system to defrost at a programmed defrost time The system will not defrost in between programmed defrost times Hence we recommend that...

Page 14: ...the software on a CD a 6 ft null modem cable a 12 ribbon cable and a detailed instruction booklet The null modem cable can be used to connect directly to a PC s serial port A modem cable must be suppl...

Page 15: ...AF 40 min 30 min 60 min when Smart Defrost is On Defrost End Temperature DEFTMP 45 F 60 F 55 F when Smart Defrost is On Alarm High Temperature ALR HI 50 F 5 F Alarm Low Temperature ALR LO 30 F 15 F Al...

Page 16: ...ure Switch Time Delay Relay 22536801 Electric Expansion Valve ESB 1 3 8 x 3 8 Conn 29320003 ESB 4 3 8 x 3 8 Conn 29320004 ESB 10 3 8 x 3 8 Conn 29320007 ESB 10 1 2 x 1 2 Conn 29320008 ESB 15 7 8 x 1 3...

Page 17: ...and Board Connection Replace as needed E2 Defrost Sensor Check Sensor and Board Connection Replace as needed E3 Suction Sensor Check Sensor and Board Connection Replace as needed E4 Suction Transduce...

Page 18: ...Correct line sizing Check for liquid line restrictions Repair line or remove restrictions Check operation of HPS Replace HPS if necessary E7 Compressor 4 Oil Pressure Safety OPS Tripped Shutdown Check...

Page 19: ...lave 3 1 COMM E9 no error no error no error 2 COMM no error E9 E9 E9 3 COMM no error no error E9 E9 4 COMM no error no error no error E9 5 COMM no error no error no error no error PROBLEM Step ACTION...

Page 20: ...13 Defrost coil and check defrost cycle see E2 settings setpoints and defrost sensor 14 Check defrost parameters 14 Correct defrost setpoints in program frequency and termination of defrosts 15 Check...

Page 21: ...21 Wiring Diagrams...

Page 22: ...22 Wiring Diagrams...

Page 23: ...23 Wiring Diagrams...

Page 24: ...ucts LLC 2175 West Park Place Blvd Stone Mountain GA 30087 770 465 5600 Fax 770 465 5990 www heatcraftrpd com Since product improvement is a continuing effort we reserve the right to make changes in s...

Reviews: