BEACON CONTROLLER
17
BEACON TROUBLE-SHOOTING GUIDE (cont’d.)
System will not run
1. Check if red jumper wire (next to blue pot) is correctly
connected across “X” terminals
2. Check red jumper wire terminals to make sure they are
connected to the wire, not the insulation
3. Check to make sure system is correctly wired
4. Check system for low voltage or high voltage conditions;
system must have voltage between 18-30 VAC for proper
operation
5. Check if “EVAP IN” & “EVAP OUT” sensors are correctly
installed on the board & on copper tubing
6. If system has Smart Controller, check “MULTI IN” & “MULTI
OUT” connection at board & at Smart Controller to make sure
wires are not reversed
7. Check if “ROOM” sensor is connected on Beacon board
8. Check that room sensor is good by resistance check
9. Check refrigerant charge
10. If voltage is too high (above 30 volts) or too low (below
18 volts), unit will not run
Coil frost pattern is uneven
1. Check evaporator coil circuits if they are feeding properly;
uneven feeding will cause uneven icing
2. If liquid line runs through cooled space, may need to be
insulated or nozzle reselected for conditions
3. If electric defrost coil for medium temperature applications,
medium temperature nozzle must be installed
Summary of Contents for 25001501
Page 22: ...BEACON CONTROLLER 22...
Page 23: ...BEACON CONTROLLER 23...
Page 24: ...BEACON CONTROLLER 24...
Page 25: ...BEACON CONTROLLER 25...
Page 26: ...BEACON CONTROLLER 26...
Page 27: ...BEACON CONTROLLER 27...
Page 28: ...BEACON CONTROLLER 28...
Page 29: ...BEACON CONTROLLER 29...
Page 30: ...BEACON CONTROLLER 30...
Page 31: ...BEACON CONTROLLER 31...
Page 32: ...BEACON CONTROLLER 32...
Page 33: ...BEACON CONTROLLER 33...
Page 34: ...BEACON CONTROLLER 34...
Page 35: ...BEACON CONTROLLER 35 Notes...