HEAT & GLO • PHOENIX42-IFT Installation Manual • 4096-901 Rev. A
• 02/18
16
C. Use of Elbows
•
A maximum of three 90° elbows (or six 45°) may be
used in any vent configuration.
•
Each 90° elbow, whether installed vertically or hori
-
zontally, counts as two feet towards the total vent run.
•
Each 45° elbow, whether installed vertically or hori
-
zontally, counts as one foot towards the total vent run.
• Elbows may be placed back to back anywhere in the
system.
•
Any 90° elbow may be replaced with two 45° elbows.
WARNING:
Elbows may NOT be installed in a downward
ditection.
Figure 4.3 shows the vertical and horizontal offsets for
SLG elbows.
B. Approved Pipe
This appliance is approved for use with Hearth & Home
Technologies SLG venting system. Refer to Section 12.A
for vent component information and dimensions.
DO NOT
mix pipe, fittings or joining methods from differ
-
ent manufacturers.
The pipe is tested to be run inside an enclosed wall.
There is no requirement for inspection openings at each
joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-
ance requires a separate vent.
DO NOT vent to a pipe
serving a separate solid fuel burning appliance.
Figure 4.3 Vertical and Horizontal Offset for SLG Elbows
16-5/8 in
(423 mm)
6-7/8 in
(174 mm)
15-3/4 in
(399 mm)
15-3/4 in
(399 mm)
45º SLG Elbows
90º SLG Elbows