PART 7: GAS PIPING
(CONTINUED)
D. CHECK INLET GAS PRESSURE
The Gas Valve is equipped with an Inlet Gas
Pressure Tap that can be used to measure the
gas pressure to the unit. To check Gas Pressure
perform the steps listed below:
1. Before you connect to the inlet pressure you
must shut off the gas and electrical power to
unit.
2 Loosen the pressure tap with a small
screwdriver. Refer to Figures 7-2, 7-3 and 7-4
for location.
3. Each unit is equipped with a needle valve
that will accept a 5/16 ID hose to connect to
a digital manometer or liquid gauge to
measure incoming pressure from 0-35” w.c.
4. Turn on the Gas and Power up the unit.
5. Put the unit into manual service mode
(Details on service mode in back of this
manual). In service mode, monitor pressure
to assure it does not drop below 1 inch from
its idle reading. If Gas Pressure is out of range
or pressure drop is excessive, contact the gas
utility, gas supplier, qualified installer or
service agency to determine correct action
that is needed to provide proper gas pressure
to the unit. If Gas Pressure is within normal
range proceed to Step 6.
6. Exit Service mode, then turn power off and
shut off gas supply at the manual gas valve
before disconnecting the hose from the gas
monitoring device. Tighten the screw on the
pressure tap tightly and turn gas on and
checks for leaks with soapy solution.
It is recommended that a soapy solution be used
to detect leaks. Bubbles will appear on the pipe
to indicate a leak is present. The gas piping must
be sized for the proper flow and length of pipe,
to avoid pressure drop. Both the gas meter and
the gas regulator must be properly sized for the
total gas load. If you experience a pressure drop
greater than 1" w.c. (.87 kPa), the meter, regula-
tor or gas line is undersized or in need of serv-
ice. You can attach a manometer to the incom-
ing gas drip leg, by removing the cap and
installing the manometer. The gas pressure
must remain between 3.5" (.87 kPa) and 14" (3.5
kPa) during stand-by (static) mode and while in
operating (dynamic) mode.
If an in-line regula-
NATURAL GAS SUPPLY PIPING CAPACITY CHART
(0.6 specific gravity gas; 0.5” WC pressure drop)
*Schedule 40 iron pipe size in nominal inch size
Boiler Model
1 Boiler
2 Boilers 3 Boilers 4 Boilers 5 Boilers 6 Boilers 7 Boilers 8 Boilers
Cubic Ft. Hr.
300
600
900
1200
1500
1800
2100
2400
ModCon 300 VWH @ 100’ of pipe
1 1/4”
1 1/2”
2”
2 1/2”
2 1/2”
2 1/2”
3”
3”
ModCon 300 VWH @ 250’ of pipe
1 1/2”
2”
2 1/2”
3”
3”
3”
4”
4”
Boiler Model
1 Boiler
2 Boilers 3 Boilers 4 Boilers 5 Boilers 6 Boilers 7 Boilers 8 Boilers
Cubic Ft. Hr.
500
1000
1500
2000
2500
3000
3500
4000
ModCon 500 VWH @ 100’ of pipe
1 1/2”
2”
2 1/2”
3”
3”
3”
4”
4”
ModCon 500 VWH @ 250’ of pipe
2”
2 1/2”
3”
3”
4”
4”
4”
4”
Boiler Model
1 Boiler
2 Boilers 3 Boilers 4 Boilers 5 Boilers 6 Boilers 7 Boilers 8 Boilers
Cubic Ft. Hr.
850
1700
2550
3400
4250
5100
5950
6800
ModCon 850 VWH @ 100’ of pipe
2”
2 1/2”
3”
4”
4”
4”
4”
5”
ModCon 850 VWH @ 250’ of pipe
2 1/2”
3”
4”
4”
5”
5”
5”
5”
Table 7-1
C. GAS TABLE
Refer to Table 7-1 to size the supply piping to
minimize pressure drop between meter or
regulator and unit.
Maximum Capacity of Pipe in Cubic Feet of Gas
per Hour for Gas Pressures of 0.5 w.c. or Less and
a Pressure Drop of 0.3 Inch w.c.
GAS-FIRED HOT WATER SUPPLY BOILER
Boiler Manual
40
Summary of Contents for MODCON VWH 300 HL
Page 23: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 22 ...
Page 24: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 23 ...
Page 25: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 24 ...
Page 26: ...PART 5 BOILER PIPING CONTINUED GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual 25 ...
Page 28: ...27 GAS FIRED HOT WATER SUPPLY BOILER Boiler Manual PART 5 BOILER PIPING CONTINUED ...
Page 75: ...LP 172 REV 2 16 06 74 ...
Page 76: ...LP 172 REV 2 16 06 75 ...
Page 77: ...MAINTENANCE NOTES 76 ...
Page 78: ...MAINTENANCE NOTES 77 ...
Page 79: ...MAINTENANCE NOTES 78 ...
Page 80: ... 2003 2009 Heat Transfer Products Inc www HTproducts com LP 276 REV 11 25 09 ...