059063–00 REV. C
|
57
SQ 8T—BACNET VARIABLE LIST
DESCRIPT
ID
OBJECT
TYPE
VALUE
NAME
UNITS
VALUE
MIN
VALUE
MAX
DEFINITION
Outdoor Temp
100
Analog
Read
ODTEMP
Degree F
32000 = OPEN
32001 = SHORT
System Temp
200
Analog
Read
SYSSEN
Degree F
32000 = OPEN
32001 = SHORT
Return Temp
300
Analog
Read
RTNSEN
Degree F
32000 = OPEN
Control Status
400
Multistate
Read
CSTAT
1
15
1=SHUTDOWN,
2=NO TSTAT CALL,
3=PROVE FAILURE,
4=SHUTDOWN BY EMS,
5=WAITING FOR PROVE,
6=SENSOR FAULT,
7=LAST STAGE HOLD,
8=DHW CALL,
9=SUMMER,
10=BOOST MODE,
11=SYSTEM RUNON,
12=SETBACK MODE,
13=OUTDOOR CUTOFF,
15=NORMAL
Season
500
Multistate
Read /
Write
SEA
1
2
1= Winter, 2= Summer
Reset Ratio
600
Multistate
Read /
Write
RRATIO
1
11
1 = 1.00 OD = 4.00 Sys,
2 = 1.00 OD = 3.00 Sys,
3 = 1.00 OD = 2.00 Sys,
4 = 1.00 OD = 1.50 Sys,
5 = 1.00 OD = 1.25 Sys,
6 = 1.00 OD = 1.00 Sys,
7 = 1.25 OD = 1.00 Sys,
8 = 1.50 OD = 1.00 Sys,
9 = 2.00 OD = 1.00 Sys,
10 = 3.00 OD = 1.00 Sys,
11 = 4.00 OD = 1.00 Sys
Set Point
700
Analog
R/W
SETPT
Degree F
-10
230
Outdoor Cutoff
800
Analog
Read /
Write
ODCUT
Degree F
19
101
Integer Values Only (19,20,21…)
Target Offset
900
Analog
Read /
Write
OFF
Degree F
-40
40
Integer Values Only (- 1,0,1,2…)
Min Target
1000
Analog
Read /
Write
MINTGT
Degree F
70
180
Integer Values Only (50,51,52…)
Max Target
1100
Analog
Read /
Write
MAXTGT
Degree F
90
240
Integer Values Only (70,71,72…)
Min Return
1200
Analog
R/W
MINRTN
Degree F
70
180
Return Lag
1300
Analog
R/W
RTNLAG
Minutes
0
30
Reaction Time
1400
Analog
Read /
Write
RETIME
Minutes
1
10
Integer Values Only (0,1,2,…)
Purge Delay
1500
Analog
Read /
Write
PURDLY
Minutes
1
10
1 thru .9 after Integer Values Only
(1,2,3…)
Minimum Run
Time
1600
Analog
Read /
Write
MINRUN
Minutes
1
60
Integer Values Only (1,2,…)
13
BACNET