background image

®

Heat

Link

www.heatlinkgroup.com

Toll Free: 1-800-661-5332
Canada Fax: 1-866-450-1155
USA Fax: 1-800-869-6098

©2013 HeatLink Group Inc.

L646544U

2013-01-08

#46544 Digital Thermostat

User Guide - Page 1 of 4

Parameter Number
Parameter Menu

Temperature Unit

Type of Sensor Used and
Temperature Displayed
(see legend below)

Regulation = Internal or external ambient sensor.

Regulation = Floor sensor.

Regulation = Internal sensor with fl oor limitation.

View of the external sensor temperature.

Plus Button

Lock Indicator

Cooling Demand Indicator

Heat Demand Indicator

COMFORT MODE

AUTO-SETBACK MODE

SETBACK MODE

FREEZE PROTECTION MODE

TIMER MODE

OFF MODE

Left Button

Minus Button

Back Button

Right Button

Edition Button

OK Button and Status LED

Status LED

Solid Red (when backlight is lit up) = heating demand
Solid Green (when backlight is lit up) = cooling demand
Flashing Red = sensor error
Flashing Green = waiting for input

The

 46544 HeatLink Digital Thermostat

 is a 24Vac electronic 

thermostat designed to provide accurate temperature control of hydronic 
fl oor heating systems. Features include:

•  Large 2" (50 mm) backlit LCD display, with a large temperature display.

•  Proportional plus Integral (PI) controlled temperature regulation. 

Proportional moves quickly to the desired setpoint and slows 
down when the desired setpoint is near. Integral compensates the 
proportional offset (overshoot) and stays close to the setpoint.
Output signal is either Pulse Width Modulation (PWM) or Hysteresis 
(on/off).

•  Fast switching between modes; temperature setpoint is adjustable at 

the press of a button.

•  Accepts timer signal for automated setback operation (requires 46643 

Timer Thermostat or 46673 Heat/Cool Thermostat).

•  Floor warming functionality is available through NTC terminal by adding 

an optional 10K fl oor sensor; the sensor acts as a fl oor temperature 
limiter (min / max fl oor temperatures are adjustable in the Parameter 
Menu). 

Technical Information

Measured temperature precision

0.1°C (or 0.2°F)

Operating temperature

0 to 40°C (or 32 to 104°F)

Setting temperature range

5 to 37°C by 0.5°C step
(or 41 to 99°F by 0.5°F step)

Regulation characteristics

Proportional Integral regulation or 
Static differential
(see Installer Parameters 
L646544N)

Electrical protection

Class II - IP30

Power supply

24 Vac +/- 10%

Output

TRIAC output 24 VAC, 15 W max.
(4 actuators)

External sensor
(sold separately)

NTC (10K Ohms)