Gas Information
A. Gas Pressure Requirements
Pressure requirements for VRT-AUB fireplaces are shown
in the table below.
Two taps are provided on the right hand side of the gas
control for a test gauge connection to measure the inlet
and outlet pressures.
The fireplace and its individual shut-off valve must be dis-
connected from the gas supply piping system during any
pressure testing of the system at test pressures in excess
of 6 mbar.
If the fireplace must be isolated from the gas supply pip-
ing system by closing an individual shut-off valve, it must
be of the handle-less type.
WARNING! Risk of Explosion!
An in-line regulator
MUST be installed if the gas pressure exceeds 3.7 kPa.
Failure to install a regulator could damage valve.
Incoming gas line should be piped into the valve compart-
ment and connected to the ISO 7-Rp 1/2 (BSP Rp 1/2)
threaded gas inlet connection on the manual shutoff valve.
Leak test all gas line points and the gas control valve prior
to and after starting the gas appliance.
B. Gas Connection
Note:
Have the gas supply line installed in accordance with
local building codes by a qualified installer approved and/or
licensed as required by the locality.
Note:
Before the first firing of the appliance, the gas supply
line should be purged of any trapped air.
Note:
Consult local building regulations to properly size the
gas supply line leading to the (Rp 1/2 in.) hook-up at the unit.
WARNING
CHECK FOR GAS LEAKS
Explosion Risk
Fire Risk
Asphyxiation Risk
• Check all fittings and connections.
• Do not use open flame.
• After the gas line installation is complete, all
connections must be tightened and checked
for leaks with a commercially-available, non-
corrosive leak check solution. Be sure to rinse
off all leak check solution following testing.
Fittings and connections may have loosened
during shipping and handling.
WARNING
Fire Risk
Explosion Risk
High pressure will damage valve.
• Disconnect gas supply piping BEFORE
pressure testing gas line at test pressures
above 6 kPa.
• Close the manual shutoff valve BEFORE
pressure testing gas line at test pressures
equal to or less than 6 kPa.
Natural Gas
Propane
Inlet Gas Pressure
1.13 - 3.40 kPa 2.75 - 3.40 kPa
Outlet (Manifold) Gas
Pressure
.80 - .95 kPa
2.36 - 2.61 kPa
Max. Gas Consumption
26.7 mJ
24.5 mJ
Burner Injector
2.53 mm
1.45 mm
Burner Air Shutter
13 mm
11.5 mm
An in-line regulator MUST be installed if the gas pressure
exceeds
3.40 kPa
. Failure to install a regulator could
damage valve.
I
MPORTANT NOTICE:
(Items 1, 2 and 3 applies to
ALL Heat & Glo gas appliances)
1. 1/2 in. GAS LINE:
Run through cavity 70 mm
above finished hearth level,
NOT RIGID, NOT
CLIPPED,
with minimum 500 mm into cavity and
120 mm back from plaster face.
2. PVC (COMPOSITE) GASLINE
must terminate
minimum 500 mm short of gas heater. Copper pipe
MUST
be the final connection to the gas heater.
3. ISOLATING SWITCH:
Location within 1 metre
of fireplace, subject to mantelpiece etc. Check to
ensure it remains clear of any mantelpiece instal-
lation.