Heat & Glo VRT-BZ-N-AUB Owner'S Manual Download Page 23

23

Heat & Glo  •  VRT-AUB  •  2123-980  Rev. H  •  5/12

A.  Flue Components

These  models  are  approved  to  use  Hearth  &  Home 

Technologies series pipes, components and termination. 

Approved components are labeled for identification. This 

pipe is tested and listed as an approved component of 
the stove.

DO  NOT  USE  FIELD-FABRICATED  FLUE  COMPO-
NENTS

. Refer to the flue manufacturer’s instructions.

This  product  is  approved  to  be  flued  either  horizontally, 
through the side wall or vertically through the roof. You may 
flue through a Class A or masonry chimney if an approved 
adapter is used. 

This gas stove is a balanced flue gas stove.  All combus-

tion air must come directly from the outside of the building.  

The flue pipe for this unit consists of an inner and an outer 

pipe.  The inner pipe carries the gas stove exhaust out of 

the system, and the outer pipe brings fresh combustion air 

into the gas stove.

•  A 

round  support  box/wall  thimble  or  heat  shield

  is 

required when the flueing passes through a combustible 

wall.

•  A 

support box or ceiling firestop

 is required when the 

flueing passes through a combustible ceiling.

•  Roof flashing and a storm collar are required when flueing 

passes through the roof.

•  Follow instructions provided with the flueing for installation 

of these items.

Flue Information 

 

Fire Hazard.
Explosion Risk.
Asphyxiation Risk.
Do NOT connect this gas stove to a chimney 

flue serving a separate solid-fuel or gas burning 

gas stove.
•  Flue this gas stove directly outside.
•  Use separate flue system for this gas stove. 
May impair safe operation of this gas stove or 

other gas stoves connected to the flue.

CAUTION

ALL flue configuration specifications MUST be followed.
•  This product is tested and listed to these specifications.
•  Appliance performance will suffer if specifications are not  

followed.

B.  Use of Elbows

Figure 7.1

C.  Measuring Standards

Vertical and horizontal measurements were made using 

the following standards.
•  Pipe measurements are from center line to center line.
•  Horizontal  terminations  are  measured  to  the  outside 

edge of termination cap.  See Figure 7.3.

•  Horizontal pipe should be installed level with no rise. 

WARNING

Diagonal runs have both vertical and horizontal flue aspects 

when calculating the effects. Use the rise for the vertical as-

pect and the run for the horizontal aspect (see Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow. 

On 45º runs, 12 in. (305 mm) of diagonal is equal to 8-1/2 

in. (216 mm) horizontal run and 8-1/2 in. (216 mm) vertical 

run. A length of straight pipe is allowed between two 45º 

elbows (see Figure 7.1).

Horizontal

Vertical

8-1/2 in.

(216 mm)

8-1/2 in. (216 mm)

12 in.

(305 mm)

Summary of Contents for VRT-BZ-N-AUB

Page 1: ...nst this appliance Keep clothing furniture draperies and other flammable materials away This is a room sealed appliance and no other ventilation is required than what is provided DO NOT DISCARD THIS M...

Page 2: ...authorities requirements for gas electrical and building regulations This appliance and its components are tested and safe when installed in accordance with this Installation Manual Report to your dea...

Page 3: ...safety reliability and efficiency As the owner of a new fireplace you ll want to read and carefully follow all of the instructions contained in this owner s manual Pay special attention to all caution...

Page 4: ...e and Components 18 5 Framing and Clearances A Selecting Appliance Location 19 B Optional Stone Surround Installed 20 6 Termination Locations A Vent Termination Minimum Clearances 21 7 Flue Informatio...

Page 5: ...IntelliFire PlusTM Ignition System Wiring 55 C Optional Accessories Requirements 55 D Blower 56 E Control Module Operation 57 13 Troubleshooting A IntelliFire Plus Ignition System 65 14 Reference Mat...

Page 6: ...d is not covered under warranty Damage to printed plated or enamelled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated...

Page 7: ...ed under warranty Damage to printed plated or enamelled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from...

Page 8: ...or weather damage which is the result of but not limited to improper chimney or venting installation HOW TO CLAIM To make a claim against this warranty contact your local distributor during regular bu...

Page 9: ...terials G Electrical Codes All electrical safety testing has been done following the EN 60335 2 102 standard Local codes apply The Heat Glo gas appliances discussed in this Installer s Guide have been...

Page 10: ...and that the integral barrier is in place WARNING Risk of Fire or Asphyxiation DO NOT op erate fireplace with fixed glass assembly removed This appliance is not intended for use by persons including...

Page 11: ...U SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improp...

Page 12: ...emote control RC300AU is programmed to the control module Note that the control module will always ignite the fireplace on HI and remain so for the initial 10 seconds of operation If the HI LO is swit...

Page 13: ...may release an odor for the first several hours This is caused by the curing of materials from manufacturing Odor may also be released from finishing materials and adhesives used near the fireplace T...

Page 14: ...maintained your fireplace will give you many years of trouble free service We recommend an nual service by a qualified service technician Doors Surrounds Fronts Frequency Annually By Homeowner Tools...

Page 15: ...r to Section 9 G for log placement instructions Verify correct log placement and no flame impingement causing sooting Correct as necessary Firebox Frequency Annually By Qualified Service Technician To...

Page 16: ...carryover to all ports Verify that there is no ignition delay Inspect for lifting or other flame problems Verify air shutter setting is correct See Section 9 for required air shutter setting Verify ai...

Page 17: ...ON 8 C VERTICAL TERMINATION CAP SECTION 10 L VENT PIPE PENETRATES ROOF PREFERABLY WITHOUT AFFECTING ROOF RAFTERS SECTION 8 FRAMING HEADED OFF IN CEILING JOISTS SECTION 8 C GAS LINE SECTION 11 VENT PIP...

Page 18: ...arts could impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry C Tools and Supplies Needed Before beginning the installation be sure that the following...

Page 19: ...uld be locat ed out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Illustrations diagrams are not drawn to scale A...

Page 20: ...Risk Odor Risk Tipping Risk Install gas stove on a stable level platform floor strong enough to support gas stove without tipping USE wood flooring ceramic tile brick hearth or high pressure laminate...

Page 21: ...nstallation with both gas and wood or fuel oil terminations the wood or fuel oil termination cap must be higher than the gas termination cap Figure 6 1 Minimum Height From Roof To Lowest Discharge Ope...

Page 22: ...s up to 50 MJ h input 12 300 Appliances over 50 MJ h input 20 1 2 500 b From the ground or above a balcony 12 300 c From a return wall or external corner 20 1 2 500 d From a gas meter M 39 1000 e From...

Page 23: ...ith the flueing for installation of these items 7 Flue Information Fire Hazard Explosion Risk Asphyxiation Risk Do NOT connect this gas stove to a chimney flue serving a separate solid fuel or gas bur...

Page 24: ...AL FLUE V 38 ft 11 58 m Maximum STRAIGHT OUT HORIZONTAL FLUE H 2 ft 610 mm Maximum For Natural Propane and Butane Gases For Natural Propane and Butane Gases Note For this type of installation the vert...

Page 25: ...Maximum 1 1 2 ft 457 mm 3 ft 914 mm 3 ft 914 mm 6 ft 1 83 m 4 1 2 ft 1 37 m 9 1 2 ft 2 88 m 6 ft 1 83 m 12 ft 3 66 m V H Max 38 ft 11 58 m H Max 12 ft 3 66 m Propane One 90 Elbow System V Minimum H M...

Page 26: ...wo 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 15 in 390 mm 2 1 4 in 690 mm 3 ft 914 mm 30 in 750 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft 1 83 m 5 ft 1 5...

Page 27: ...4 57 m Propane Two 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 15 in 390 mm 2 1 4 in 69 cm 3 ft 914 mm 30 in 750 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft...

Page 28: ...mm 2 ft 610 mm 4 ft 1 22 m 3 ft 914 mm 6 ft 1 83 m 4 ft 1 22 m 8 ft 2 44 m 5 ft 1 52 m 10 ft 3 05 m V1 V2 H Max 36 ft 10 97 m H Max 10 ft 3 05 m Propane Two 90 Elbows System V Minimum H1 H2 Maximum 2...

Page 29: ...ree 90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 1 ft 305 mm 2 1 4 in 690 mm 3 ft 914 mm 2 ft 610 mm 4 1 2 ft 1 37 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 7 ft 2 13 m 6 ft 1 83 m 6 ft 1 83...

Page 30: ...90 Elbows System V Minimum H Maximum H1 H2 Max 1 1 2 ft 457 mm 1 ft 305 mm 1 3 4 ft 530 mm 3 ft 914 mm 2 ft 610 mm 3 1 2 ft 1 07 m 4 1 2 ft 1 37 m 3 1 2 ft 1 07 m 5 1 2 ft 1 68 m 6 ft 1 83 m 6 ft 1 8...

Page 31: ...s to engage pipe then rotate counterclockwise to lock Step 1 Balanced flue pipe is designed with a locking connection To connect the flue system to the gas stove flue outlet Lock the flue components i...

Page 32: ...SHIELD OVER TOP HALF OF PIPE INTERIOR WALL 2 in 51 mm clearance from rear of stove WALL THIMBLE MINIMUM OF 6 in 152 mm OF PIPE THROUGH THE WALL PIPE LENGTH PIPE LENGTH TRIM RING 90 ELBOW O Place m ark...

Page 33: ...m clearance maintained to combustibles from the top of the heat shield Ensure that framing on the inside of the wall is a minimum inner framing diameter of 9 in x 9 in 229 mm x 229 mm The four trim ri...

Page 34: ...D TO WALL STRAP WALL STRAP TWO 45 DEGREE ELBOWS METAL STRAP Step 2 Set the gas stove in its desired location Drop a plumb bob down from the ceiling to the position of the gas stove flue exit and mark...

Page 35: ...ble cover in a flat ceiling cut a 229 mm square hole in the ceiling centered on the hole drilled in Step 2 Frame the hole as shown in Figure 7 22 ROUND CEILING SUPPORT BOX WALL THIMBLE COVER 229 mm x...

Page 36: ...ical Flue Restrictor If the fireplace installation requires a vertical flue off the top of the unit with no horizontal flue or elbows the vertical flue restrictor must be added Reinstall heat shield w...

Page 37: ...must be placed on each side of an interior wall A minimum 1 1 2 inch 38 mm overlap of attached heat shields must be maintained See Section 10 H for information for regarding the in stallation of a hor...

Page 38: ...pipe only Frame opening 9 in x 9 in 229 mm x 229 mm whenever the vent penetrates a ceiling floor see Figure 8 3 Frame the area with the same sized lumber as used in ceiling floor joist The ceiling fir...

Page 39: ...tion from getting between the shield and vent pipe and to maintain air space clearance Figure 8 5 Attic Insulation Shield Vaulted Ceiling Installation Remove one shield from box NOTICE Cut previously...

Page 40: ...he two screws in the front of the bottom plate and the two screws holding the metal strap across the back of the gas stove Refer to Figure 9 2 for locations Figure 9 1 Figure 9 2 C Leveling and Boltin...

Page 41: ...er collar and screws 3 Remove and retain the Allen head screws that hold the solid back panel in place Figure 9 8 Remove and discard the solid back panel Figure 9 7 E Top to Rear Flue Conversion KIT C...

Page 42: ...the top of gas stove with screws previously removed Figure 9 9 Figure 9 9 ON BACK OF APPLIANCE 6 Remove the four screws from the cover plate on rear of gas stove Set cover plate aside Retain screws S...

Page 43: ...ur gas stove Figure 9 13 Place log 1 into the cradle in the burner Lean the log back towards right corner of firebox Figure 9 14 Locate log 2 over the pin in log 1 and into notch in log 1 Lean the log...

Page 44: ...17 Position the four flat 6 mm spacer washers on the front door so that the four mounting screws pass through them Position the glass over the front door Install the four protective barrels into the g...

Page 45: ...and bottom N Adjustments And Replacement Parts Adjustments and replacement parts for this appliance should only be done by a qualified service person A wir ing diagram for the appliance is shown in Se...

Page 46: ...ted and locked into the preceding component Commercial Multi family Multi level exceeding two sto ries or High Rise Applications For Installation into a commercial multi family multi level exceeding t...

Page 47: ...d the outer flue of the slip section over the outer flue of the pipe section See Figure 10 3 Slide together to the desired length Figure 10 3 Slip Section Pilot Holes Figure 10 4 Screws into Slip Sect...

Page 48: ...system on the ceiling and drill a small hole through the ceiling and roof at this point Locate the hole and mark the outline of the cathedral ceiling support box on the outside roof Remove shingles or...

Page 49: ...for horizontal runs Place the pipe supports around the flue pipe Nail the pipe supports to the framing members For Vertical Runs The flue system must be supported every 8 ft 2 44 m above the fireplace...

Page 50: ...Shield 38 mm min overlap Outer Flue H Flue Termination For Horizontal Terminations using the SLP TRAP To attach and secure the termination to the last section of horizontal flue The rear flue heat shi...

Page 51: ...the heat shields on the cap and wall shield firestop must be trimmed A minimum 1 1 2 in 38 mm overlap MUST be maintained Use an extended heat shield if the finished wall thickness is greater than 7 1...

Page 52: ...Locate and mark the flue center point on the underside of the roof and drive a nail through the center point Make the outline of the roof hole around the center point nail The size of the roof hole fr...

Page 53: ...ading to the Rp 1 2 in hook up at the unit WARNING CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Check all fittings and connections Do not use open flame After the gas line installati...

Page 54: ...or Explosion Support control when attaching pipe to prevent bending gas line A small amount of air will be in the gas supply lines WARNING Risk of Fire or Explosion Gas build up dur ing line purge cou...

Page 55: ...e appliance WARNING Risk of Shock or Explosion DO NOT wire IPI controlled appliance junction box to a switched circuit Incorrect wiring will override IPI safety lockout Refer to Figure 12 1 IPI Wiring...

Page 56: ...wer door Use of the fan requires that the Junction Box factory installed be connected to 220 240 VAC service before permanently enclosing the fireplace The access hole for connecting the service wires...

Page 57: ...remote control RC300AU is programmed to the control module Note that the control module will always ignite the fireplace on HI and remain so for the initial 10 seconds of operation If the HI LO is swi...

Page 58: ...chnician This remote control is tested and safe when installed in accordance with this installation manual Do not install any components that may be damaged Do not modify disassemble or substitute any...

Page 59: ...ange the indicators on the room temperature and set temperature portion Note This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the...

Page 60: ...ol module will beep once 5 seconds later when ready See Figure 7 Using a small item such as a paper clip press and release the LEARN button located near the ON OFF REMOTE switch See Figure 12 11 Contr...

Page 61: ...no but tons are pressed within 5 seconds Press any button to resume full functionality In idle mode only active func tions will show on the screen Standby mode The remote control will go into a standb...

Page 62: ...ber the previous FLAME HEIGHT setting and will automatically adjust after 10 seconds Adjusting Fan Speed Press the MENU button to activate the menu Using the UP and DOWN arrows highlight the FAN icon...

Page 63: ...child lock feature NOTICE No functions will be usable until child lock feature is disabled Power Outage If fireplace battery backup system IS installed at time of power outage fireplace operation wil...

Page 64: ...r button is pressed verify that the control module is plugged in the fire place junction box located in the controls area Also verify that the batteries are installed in the battery pack Fan does not...

Page 65: ...or 1 8 in 3 mm 2 Pilot won t light there is no noise or spark A No power transformer installed incorrectly or depleted batteries Verify that transformer is installed and plugged into module Check vol...

Page 66: ...sense lead is at least 0 14 microamps Verify correct pilot orifice is installed and gas inlet is set to pressure specifi cations Polish flame sensing rod with fine steel wool to remove any contaminan...

Page 67: ...re actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Section 5 Figure 14 1 Appliance Dimensions A B G F H E Hearth Pad D C I Height includes 9 5 mm hear...

Page 68: ...h Pad B Appliance Dimension with Stone Surround Diagram Figure 14 2 Appliance Dimensions with Stone Surround Height includes 9 3 mm hearth pad Height includes 9 53 mm hearth pad A B C D E F G Inches 3...

Page 69: ...nspect for paint condition warpage corrosion or perforation Sand and repaint as necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly s...

Page 70: ...2 12 305 SLP24 24 610 SLP36 36 914 SLP48 48 1219 SLP6A 2 6 51 152 SLP12A 2 12 51 305 8 3 4 in 222 mm 6 1 2 in 165 mm 6 5 8 in 168 mm SLP45 45 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal...

Page 71: ...izontal Termination Cap 15 1 8 in 384 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall...

Page 72: ...ect Vent Vertical Stove Beginning Manufacturing Date March 2011 Ending Manufacturing Date ______ VRT AUB VRT GY N AUB VRT BZ N AUB VRT GY P AUB VRT BZ P AUB Part number list on following page Log Set...

Page 73: ...23 120 10 Burner N 2123 017 Burner P 2123 022 11 Glass Frame Assembly 2123 005 12 Front Door Assembly Bronze 2123 028 Gray 2123 016 13 Latch Assembly Lower Pkg of 2 33858 2 14 Valve Assembly Refer to...

Page 74: ...lot Assembly N 2198 014 Pilot Assembly P 2198 015 14 3 Pilot Bracket 2123 140 14 4 Burner Support 7031 279 14 5 3 Hole Grommet 2118 420 14 6 Valve Bracket 2189 117 14 7 Flex Ball Valve Assembly 2098 3...

Page 75: ...__________________________________________________________________ ________________________________________________________________________________ ____________________________________________________...

Reviews: