Figure 18.

Attic Firestop

Installing the Stove 

(continued)

Installation 

(suite)

C.  Vent Termination
For Horizontal Terminations -

 To attach and secure 

the termination to the last section of horizontal vent:
•    Rotate  and  interlock  the  ends  as  described  at 

the beginning of the Installing Vent Components 

section.

•    The termination kit should pass through the wall 

firestops from the exterior of the building.

•    Adjust  the  termination  cap  to  its  final  exterior 

position on the building.

If the area above the ceiling is 

NOT

 an attic, position 

and secure the ceiling firestop on the ceiling side of 

the previously cut and framed hole.

This  shows  a  ceiling 

installation.
If  the  area  above  the 

ceiling 

IS

 an attic, position 

and  secure  the  firestop 

on  top  of  the  previously 

framed hole.

This shows an attic 

installation.
1.  Keep  insulation  away 

from  the  vent  pipe  at 

least 1 inch (25.4 mm)

Figure 17.                

Ceiling Firestop 

(Ceiling Side)

Si  l’espace  au-dessus  du  plafond

  N’EST  PAS

  un 

grenier,  poser  et  fixer  le  coupe-feu  du  côté  plafond 

dans le trou préalablement découpé et encadré.

Installation au plafond 
Si  l’espace  au-dessus  du 

plafond 

EST

  un  grenier, 

poser et fixer le coupe-feu 

au-dessus 

du 

trou 

préalablement  découpé  et 

encadré.

C. Mitres
Mitres horizontales - 

Pose de la mitre sur la dernière 

section d’un conduit horizontal:
•   Faire pivoter et verrouiller les extrémités selon les 

instructions données au début de la section Pose 

du système de ventilation.

•   Faire  passer  le  kit  de  mitre  par  les  coupe-feu 

muraux à partir de l’extérieur du bâtiment.

•   Placer la mitre à l’emplacement prévu à l’extérieur 

du bâtiment.

Figure 18.

Coupe-feu de grenier

Figure 17.

Coupe-feu de plafond 

(côté plafond)

Installation de grenier

1.  Laisser  un  espace  d’au 

moins  25.4mm  (1 in.)  entre 

l’isolant et le conduit.

NAILS (4 REQUIRED) /

CLOUD (4)

RAFTER/

CHEVRON

CEILING/

PLAFOND

CEILING FIREST OP/

COUPE-FEU

DE PLAFOND

JOIST/

SOLIV E

CEILING FIREST OP/

COUPE-FEU

DE PLAFOND

NAILS (4 REQUIRED) /

CLOUS (4)

CEILING/

PLAFOND

Summary of Contents for TIARA I

Page 1: ...z imm diatement votre fournis seur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournis seur de gaz appelez le service des incendies L installation et...

Page 2: ...Servicing Your Stove 40 thru 42 Consignes de s curit 3 4 Liste des pi ces de rechange 5 Section 1 Homologations et codes d installation 6 Certifications 6 Codes d installation 6 Installations haute a...

Page 3: ...fore installing or operating this appliance This Install ers Guide must be left with appliance for future reference AVERTISSEMENT Une installation un r glage une modification un entretien ou une maint...

Page 4: ...de l appareil soit toujours D GAG de tout obstacle pour permettre l entretien et assurer un fonctionnement correct Etant donn sa temp rature lev e installer l appareil L CART des zones de passage des...

Page 5: ...Piezo 842 0361 19 Glass Door Assembly Module de Porte en verre 844 9300 20 Log Set Assembly Jeu de buches 844 9320 Pilot Orifice NG Orifice de vielleuse GN Pre 20000 571 516 Post 20000 842 4260 Pilot...

Page 6: ...lation CAN CGA B149 au Canada L appareil doit tre mis la masse conform ment aux codes locaux ou en l absence de ces derniers conform ment au National Electric Code ANSI NFPA No 70 aux tats Unis ou au...

Page 7: ...Pr sentation des appareils de chauffage Heat N Glo ventilation directe Les appareils de chauffage Heat N Glo ventilation directe sont pr vus pour aspirer l air de l ext rieur et refouler les gaz d ch...

Page 8: ...prendre l installation d un appareil de chauffage d terminer L emplacement de l appareil La configuration du syst me de ventilation La tuyauterie pour l alimentation en gaz Le c blage lectrique L enca...

Page 9: ...Mise en marche suite Figure 2 Diagram of the Tiara II Figure 2 Sch ma du mod le Tiara II 29 1 2 749mm 7 1 2 191mm 14 3 4 375mm 6 5 8 168mm 15 1 4 387mm 19 3 8 491mm 30 1 8 766mm 6 7 8 174mm 29 1 4 74...

Page 10: ...ppareil de chauffage dans une pi ce Clearance Requirements The minimum clearance to a perpendicular wall extending past the face of the stove is six inches 150mm The back of the stove may NOT be reces...

Page 11: ...learances from the Vent Pipe to Combustible Materials Distances minimum entre le conduit de ventilation et les mat riaux combustibles For Horizontal Sections Top 3 inches Bottom 1 inch Sides 1 inch Fo...

Page 12: ...rm Aucune sp cification n exige la pr sence d ouvertures d inspection au niveau de chaque joint a l int rieur du mur Il n existe aucune sp cification de pente pour les conduits horizontaux Des autocol...

Page 13: ...ieur de 4 in et conduit ext rieur de 6 5 8 in 9 1 4 in 235mm 6 5 8 in 168mm 6 1 2 in 165mm 6 3 8 in 162mm 6 1 2 in 165mm 9 5 8 in 244mm 9 5 8 in 244mm 6 5 8 in 168mm 6 3 8 in 162mm SL 45D SL 90D SL 17...

Page 14: ...tilation vertical droit Tiara I Lorsqu une section verticale gale ou sup rieure 3 65 m 12 ft est attach e directement en haut de l appareil de chauffage un d flecteur suppl mentaire est n cessaire pou...

Page 15: ...indre sa taille et sa couleur habituelles avant que vous r gliez l obturateur d air Au fur et mesure que l obturateur se ferme la flamme devient plus haute et plus fonc e Air Shutter Adjustment Tiara...

Page 16: ...Installing the Stove continued Installation suite VERTICAL VENT VENTILATION VERTICALE V 2 610mm MIN 40 1200cm MAX Figure 7 Straight Vertical Vent System Figure 7 Syst me de ventilation vertical droit...

Page 17: ...20cm 4 MAX 120cm 18 MIN 540cm 15 MAX 450cm Tiara II VENTING WITH ONE 1 900 ELBOW VENTILATION AVEC UN 1 COUDE 900 V H 40 MAX 1200cm H 18 MAX 540cm V H 2 MIN 610mm 2 MAX 610mm 3 MIN 914mm 3 MAX 914mm 4...

Page 18: ...AX 450cm Tiara II VENTING WITH TWO 2 90o ELBOWS VENTILATION AVEC DEUX 2 COUDES 90 V V1 H 40 MAX 1200cm H 18 MAX 540cm V H 2 MIN 610mm 2 MAX 610mm 3 MIN 914mm 3 MAX 914mm 4 MIN 120cm 4 MAX 120cm 18 MIN...

Page 19: ...iara II VENTING WITH THREE 3 90o ELBOWS VENTILATION AVEC TROIS 3 COUDES 90 V V1 H H1 40 MAX 1200cm H H1 18 MAX 540cm Tiara I VENTING WITH THREE 3 90o ELBOWS VENTILATION AVEC TROIS 3 COUDES 90 Figure 1...

Page 20: ...nstructions du Guide d installation de l appareil de chauffage et les instructions des kits de ventilation pages 12 thru 22 pour s assurer que le syst me de ventilation s lectionn est correct Essayer...

Page 21: ...ng the First Vent Component to the Starting Collars 1 Mettre du ciment r frac taire 2 Aligner les filets int rieurs et tourner les sections de conduit dans le sens horaire jusqu ce qu elles se bloquen...

Page 22: ...ents Figure 13 Installing Support Brackets Continuer ajouter des sections et les verrouiller successivement Figure 12 Ajout de sections Pour poser des supports de conduit horizontal Placer les support...

Page 23: ...trou doit se trouver 25 4 mm 1 in au dessus du centre du conduit horizontal Placer les coupe feu de chaque c t du trou et les clouer ou les visser Les crans thermiques des coupe feu DOIVENT se trouver...

Page 24: ...travers par le conduit Pour poser des coupe feu de plafond Suspendre un fil plomb au dessus du centre du conduit Tracer sur le plafond un rep re correspondant au centre du conduit Percer un trou ou p...

Page 25: ...Figure 17 Ceiling Firestop Ceiling Side Si l espace au dessus du plafond N EST PAS un grenier poser et fixer le coupe feu du c t plafond dans le trou pr alablement d coup et encadr Installation au pla...

Page 26: ...TRE DOIT SE TROUVER AU MOINS 457 MM 18 IN EN DESSOUS DETOUT MAT RIAU COMBUSTIBLE BALCON DE BOIS PAR EXEMPLE ET LE C T DE LA MITRE DOIT SE TROUVER AU MOINS 152 MM 6 IN DE TOUT MUR EXT RIEUR PARALL LE L...

Page 27: ...public M 457mm Distance sous une v randa un porche une terrasse ou un balcon Figure 20 D gagements minimum de la mitre Minimum de 760 mm pour surplombs recouverts de vinyle Un conduit ne peut pas se...

Page 28: ...nt systems installed on the outside of the building Mitres verticales Pour situer le conduit et poser les sections de conduit D terminer le centre du conduit tracer un rep re sur la surface inf rieure...

Page 29: ...oof hole and to divert rain and snow from the vent system Attach a flashing to the roof using nails and use a non hardening mastic around the edges of the flashing base where it meets the roof Attach...

Page 30: ...mentation en gaz tape 4 Raccordement au gaz REMARQUE Le conduit gaz doit tre install conform ment aux codes de construction locaux L installation doit tre effectu e par un technicien qualifi et ou mun...

Page 31: ...az naturel Propane Pression d entr e Col d eau Col d eau minimum 5 0 pouces 11 0 pouces Pression d entr e Col d eau Col d eau maximum du gaz 14 0 pouces 14 0 pouces Pression au Col d eau Col d eau col...

Page 32: ...o the stove CAUTION DO NOT PULL ON THE SHIELD TO CAUSE THE ON OFF SWITCH WIRING TO BECOME DISCONNECTED 2 Set the blower on the blower bracket with the two ducts towards the back 3 Install the GFK 160A...

Page 33: ...8 Connect electrical cord into the junction box plug the junction box cord into a 110 VAC grounded outlet WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR CONTROL WIRING SYSTEM OF THIS...

Page 34: ...NORMALEMENT Figure 25 Sch mas de c blage du ventilateur si quip NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 1050 C RATED WIRE REMARQ...

Page 35: ...ove the base of the stove HEARTH EXTENSION While a hearth extension may be desirable for aesthetic reasons it is not required for gas fireplace heaters per ANSI or CSA testing standards Figure 26 Comb...

Page 36: ...mballage s par voir les instructions En cas de formation de suie repositionner l g rement les b ches pour r duire le contact avec les flammes Pose des braises Un sac de braises sont livr s avec l appa...

Page 37: ...s touching the back of the burner LOG PLACEMENT INSTRUCTIONS Model Tiara I Log Set Assembly 844 9320 LOG 2 Set Log 2 so that the left end is against the wall of the firebox and right end fits inside t...

Page 38: ...II Log Set Assembly 844 9330 LOG 1 Place log 1 in back of the stove so the notch fits over the pilot and the back of the log hits the back of the stove LOG 2 Place log 2 so the semi circle notch is i...

Page 39: ...LOG 3 Place 3 against the tab on the right wall and the tab on the burner pan Make sure no burner ports are covered in the front MODEL TIARA II CONT D LOG PLACEMENT INSTRUCTIONS LOG SET ASSEMBLY 844 9...

Page 40: ...DE S CURIT ET LES MISES EN GARDE RELATIVES L ALLUMAGE ET L UTILISATION DE L APPAREIL DE CHAUFFAGE Apr s l installation LAISSER CE GUIDE PROXIMIT DE L APPAREIL POUR POUVOIR LE CONSULTER EN CAS DE BESO...

Page 41: ...fr quence d entretien et de r vision de l appareil de chauffage d pende du volume d utilisation et du type d installation nous recommandons un examen de l appareil par un technicien qualifi au d but...

Page 42: ...itre ext rieure du syst me de ventilation de fa on r guli re pour s assurer qu aucun d bris n interf re avec l alimentation en air Inspecter compl tement le syst me de ventilation pour s assurer de so...

Page 43: ...ie 543790 586383 Canada 1 123 296 1 297 746 2 195 264 Mexique 97 0457 Nouvelle Z lande 200265 et autres brevets am ricains et trangers en instance Contacter le concessionnaire Heat N Glo pour toute qu...

Page 44: ...44 Tiara I II ATTENTIONINSTALLER PLEASE RETURN THESE INSTRUCTIONSTO THESTOVE OW NERW HENINSTALLATIONIS COMPLETED...

Reviews: