Installing the Fireplace

Step 1.       Locating the Fireplace

The diagram below shows space and clearance require-
ments for locating a fireplace within a room.

A

B

C

D

E

49”

22”

39 1/2”

56”

79”

Minimum Clearances

 from the Fireplace to Combustible Materials

Inches

mm

Glass Front ...................... 36 .................... 914
Floor ................................. 0 ...................... 0
Rear ................................ 1/2 .................... 13
Sides ............................... 1/2 .................... 13
Top ................................. 3 1/2................... 89
Ceiling* ............................ 31 .................... 787

Clearance Requirements

The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25
mm). The back of the fireplace may be recessed 21 1/2
inches (546 mm) into combustible construction.

The minimum clearance from the top face of the fireplace
to combustible finishing materials such as drywall, is 1” (25mm).

The distance from the unit to combustible construction
is to be measured from the unit outer wrap surface to
the combustible construction, 

NOT

 from the screw

heads that secure the unit together.

A

.   49”

         B

.  40 1/2”

  C

.  22”

Figure 3.

Framing Dimensions

Minimum Clearances from the B-Type Vent Pipe to
Combustible Materials is 1” (25mm) all around the pipe.

Step 2.  Framing the Fireplace

Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.

CAUTION:

 MEASURE FIREPLACE DIMENSIONS AND

VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.

Framing should be constructed
of 2 X 4 lumber or heavier.

WARNING:

To ensure proper clearances
the front framing header
must be installed on its
narrow edge and to the front
of the frame.

A

B

C

E

1/2“ MIN. (13mm)

D

B

A

C

1” MIN. (25mm)

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure  13).

Figure 2.    Fireplace Dimensions, Locations,
                     and Space Requirements

1/2” CLEARANCE FROM BACK OF
FIREPLACE TO COMBUSTIBLE

0” CLEARANCE TO

FRAMING MEMBER

0” CLEARANCE

1/2” CLEARANCE FROM BOTH SIDES

OF FIREPLACE TO COMBUSTIBLE

FRAMING

MEMBER

Summary of Contents for 8000TVD

Page 1: ...iters Laboratories Listed 379 900I 1 04 READ THIS MANUAL BEFORE INSTALLING OR OPERATING THIS APPLIANCE THIS INSTALLERS GUIDE MUST BE LEFT WITH APPLIANCE FOR FUTURE REFERENCE Please contact your Heat N...

Page 2: ...DERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the firs...

Page 3: ...ystem Approvals 13 B System Components 13 C Bedroom Installation in Canada 14 D Vent Termination 14 Step 5 Positioning Leveling and Securing the Fireplace 14 Step 6 The Gas Control Systems 14 Step 7 T...

Page 4: ...um ros de pi ce se trouve la page suivante 10 11 12 13 14 16 15 17 4 6 2 1 3 8 7 9 Log Set Assembly 18 5 NG LP Exploded Parts Diagram GN PL Vue clat e des pi ces Service Parts 8000TVD Beginning Manufa...

Page 5: ...he 1 SRV582 701 11 Log 2 B che 2 SRV582 703 12 Log 3 B che 3 SRV582 702 13 Log 4 B che 4 SRV582 704 14 Log 5 B che 5 SRV402 701 15 Log 6 B che 6 SRV582 706 16 Log 7 B che 7 SRV582 707 17 Log 8 B che 8...

Page 6: ...Allumeur pi zo 291 513 4 Pilot Assembly NG Module de veilleuse GN 485 510A 4 Pilot Assembly LP Module de veilleuse PL 485 511A 5 Valve Bracket Parenth se de Valve 550 169 6 Orifice NG 32C Assembl e d...

Page 7: ...ilot Assembly LP Module de veilleuse PL PRE 002324001 POST 002324001 385 511A 4021 026 5 Valve Bracket Parenth se de Valve PRE 002324001 POST 002324001 385 169 2025 101 6 Ground Strap Courroie de Rais...

Page 8: ...particular installation Refer to the National Fuel Gas Code ANSI Z223 1 NFPA54 1Approvals and Codes current edition The Uniform Mechanical Code current edition and local Building Officials for the op...

Page 9: ...Failure to follow these instructions will void the owner s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the followi...

Page 10: ...3 8 1026mm 9 1 8 233mm GAS LINE ACCESS 43 1091mm 48 3 8 1229mm 3 1 2 89mm 8 3 8 212mm ELECTRICAL ACCESS 21 1 2 548mm 9 1 2 241mm 35 1 2 902mm 17 3 4 450mm 6 152mm B VENT VENT COLLAR STANDOFFS HOOD GAS...

Page 11: ...ew heads that secure the unit together A 49 B 40 1 2 C 22 Figure 3 Framing Dimensions Minimum Clearances from the B Type Vent Pipe to Combustible Materials is 1 25mm all around the pipe Step 2 Framing...

Page 12: ...ely balanced to allow atmospherically vented appliances such as top vented gas fireplaces with draft hoods to draft properly If the home experiences negative pressure or is likely to experience negati...

Page 13: ...lar Look at the vent pipe through the holes in the 10 5 8 ring to check that the vent pipe is attached NOTE It is always better to first attach a straight section of vent to the unit before attaching...

Page 14: ...replace Place the fireplace into position see Figure 7 Level the fireplace from side to side and from front to back Shim the fireplace with non combustible material such as sheet metal as necessary Se...

Page 15: ...ireplace lower grille insert the gas supply line through the gas line hole and connect it to the shut off valve When attaching the pipe support the control so that the lines are not bent or torn Step...

Page 16: ...he desired position on a wall Run a maximum of 25 feet 7 8 m or less length of 18 A W G minimum wire and connect it to the fireplace ON OFF switch pigtails WARNING DO NOT CONNECT 1 10 120 VAC TO THE W...

Page 17: ...The fireplace can be used as necessary Once power 110 VAC is re stored disconnect red and black wire leads to extend bat tery life Optional Accessories Optional fan and remote control kits require tha...

Page 18: ...e materials can be used to cover up the gap between the sheet rock and the fireplace Do not obstruct or modify the air inlet outlet grilles When overlapping on both sides leave enough space so that th...

Page 19: ...8 hours This will help to cure the chemicals used in the paint and logs Heat N Glo fireplaces manufactured with tempered glass may be installed in hazardous locations such as bathtub enclo sures as de...

Page 20: ...lly By Qualified service technician Task Make a visual check of the straight flame sensor rod see Figure 33 Use emery cloth to carefully remove any existing film or white deposits Checking Flame Patte...

Reviews: